Installation

Before installing SmartSeries equipment, design the system layout taking into consideration personnel safety, operational function and convenience, and power cable length. In general, for 115 V ac systems the total power cable length should not exceed 1 mile (1.6 km), but the length of cable between the stations is not a critical factor.

However, it is a good practice to run a separate power feed to each station located in hazardous areas. With a separate feed, individual stations can be de-energized for service or maintenance without affecting the power supply and operation of the other stations in the hazardous area.

Mounting

NOTE: The mounting surface must be able to support 55 lbs (25 kg).

1.Remove the front panel. Allow the front panel to hang from the rear of the enclosure by means of two retaining straps during installation. The straps serve as personnel safety feature and as a safeguard designed to ensure the front panel flame path is not nicked, dented or otherwise damaged while mounting the enclosure.

2.To maintain the explosion-proof integrity of the enclosure, all mounting hardware is located in non- intrusive mounting holes under the front panel. The suggested mounting height of the station is 54 inches (137cm). Use standard 1/2-inch socket head cap screws or M12 bolts to secure the enclosure to a flat mounting surface. See Figure 6 below for mounting hole dimensions.

Figure 6. Shows mounting holes with dimensions.

3.After the enclosure is securely mounted, remove the plug-in amplifier:

Remove the four screws that secure the amplifier to the standoffs, and retain.

Pull the amplifier straight toward you to disengage the 16-pin connector from the enclosure.

Set the amplifier aside in a safe place while completing the installation.

NOTE: The following instructions are provided to ensure compliance with the appropriate approval standards. Select the version that applies to the equipment you have purchased based on approval agency jurisdiction.

\\s_eng\gtcproddocs\standard ioms - current release\42004 instr. manuals\42004-615l2.doc 6/97

Image 7
Contents Application How to Use the Assembly/ModelConfidentiality Notice IntroductionModel 670-801-EX/UL SmartSeries Amplifier Hardware ConfigurationModel 670-801-UL Top and Bottom Views ExternalChassis Gasket InternalBlock Diagram ACH InterfacesMounting InstallationUL Version Wiring Detail Operation AdjustmentsInternalAdjustments Troubleshooting MaintenanceSoftware Configuration 95% non-condensing SpecificationsReference to Assembly/Model Drawings Replacement PartsReference Material Return Policy Warranty