Samsung AP30M0AN AP30M0ANUMG, AP30M0ANXSG, AP30M0AXUMG, AP30M0AXXSG Connection of Refrigerant Piping, Flare Processing, Installation Method, Outer Diameter(D), 40_ installation part, 2.Remove burr on the edge of pipe

1 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Download on canonical page 50 pages, 0 b

Installation Method

Connection of Refrigerant Piping

Flare Processing

1. Cut the pipe using the pipe cutter.

Oblique

Roughness

Burr

2.Remove burr on the edge of pipe.

-If burr is not removed after cutting the pipe, there is a risk of refrigerant gas leakage.

-If foreign substance such as burr goes into the pipe, there is a risk of product breakdown.

Face the pipe downward when doing the work.3.Insert the flare nut into the pipe, and then perform the flare processing.

Pipe

Reamer

D

 

Outer Diameter(D)

A(mm)

 

ø 6.35mm

1.3

 

A

 

ø 15.88mm

2.2

 

 

Inclined

Damaged

Cracked

Uneven

 

surface

 

thickness

 

 

 

 

When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

40_ installation part