![](/images/new-backgrounds/1027633/2763375x1.webp)
GAS SUPPLY CONNECTIONS
GAS SUPPLY PIPE CONNECTIONS
Figure 41. GAS SUPPLY PIPING
1.Make sure to install ground joint union for servicing.
In Canada – When using manual main shutoff to support the weight of the piping with valves, ensure that it is identified by the installer.
2.Install drip leg (sediment trap) per NFPA 54 for US and CAN B149.1 for Canada.
3.Support the piping with hangers, not by the boiler or its accessories. The gas valve and blower will not support the weight of the piping. Failure to comply could result in severe personal injury, death, or substantial property damage.
4.Purge all air from the gas supply piping.
5.Before setting the boiler in operation, check the boiler and its gas connection for leaks.
•Disconnect the boiler from the gas supply piping system during any pressure testing, at a test pressure in excess of 1/2 PSIG (3.5 kPa)
•The boiler must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing, at test pressures equal to or less than 1/2 PSIG (3.5 kPa).
Do not check for gas leaks with an open flame, instead use the bubble test. Failure to use the bubble test or check for gas leaks can cause severe personal injury, death, or substantial property damage.
6.Use pipe sealing compound compatible with propane gases. Apply sparingly only to male threads of the pipe joints so that pipe dope does not block gas flow.
Failure to apply pipe sealing compound as detailed in this manual can result in severe personal injury, death, or substantial property damage.
7.Make sure the maximum inlet gas pressure do not exceed the value specified. Minimum value specified is for input adjustment only.
Make sure to use two wrenches when tightening gas piping at the boiler, using one wrench to prevent the boiler gas line connection from turning. Failure to support the boiler gas connection pipe to prevent it from turning could damage gas line components. Do not use wrench on valve body as damage would occur.
GAS PRESSURE REQUIREMENTS
The maximum allowable gas supply pressure for this boiler is 14 inches w.c. (3.5 kPa). Install a positive
If a positive
1.Positive
2.Positive
3.After installing the positive
4.When installing multiple boilers in the same gas supply system it is recommended that individual positive
38