A.O. Smith 3400, 2600, 1700, 2000 Domestic HOT Water, Lead LAG LL Master General Operation

Models: 3400 1700 2000 2600

1 83
Download 83 pages 55.74 Kb
Page 48
Image 48

DOMESTIC HOT WATER

Start-up sequence DHW-request (system in standby):

1.Heat request detected (either DHW Sensor Only, DHW Sensor and Remote Command or DHW Switch and Inlet Sensor, whichever applies).

2.The pump is switched on (after the DHW Pump Start Delay).

3.After a system Safe Start Check, the Blower (fan) is switched on after a dynamic ILK switch test (if enabled).

4.After the ILK switch is closed and the purge rate proving fan RPM is achieved (or High Fire Switch is closed) - prepurge time is started.

5.When the purge time is complete, the purge fan RPM is changed to the Lightoff Rate or if used, the damper motor is driven to the Low Fire Position.

6.As soon as the fan-rpm is equal to the light-off rpm (or the Low Fire Switch closes), the Trial for Ignition or Pre-Ignition Time is started (depending on configuration).

7.Pre-Ignition Time will energize the ignitor and check for flame.

8.Trial for Ignition. Specifics for timings and device actions are defined by the OEM or installer.

9.The ignition and the gas valve are switched on.

10.The ignition is turned off at the end of the direct burner ignition period, or for a system that does use a pilot, at the end (or optionally at the middle) of the Pilot Flame Establishing Period (PFEP). For an interrupted pilot system this is followed by a Main Flame Establishing Period (MFEP) where the pilot ignites the main burner. For an intermittent pilot there is no MFEP.

11.The fan is kept at the lightoff rate during the stabilization timer, if any.

12.Before the release to modulation, the fan is switched to minimum RPM for the DHW Forced Rate and Slow Start Enable, if the water is colder than the threshold.

13.At the end of the DHW-heat request the burner is switched off and the fan stays on until post purge is complete.

14.A new DHW-request is blocked for the forced off time set by the Anti Short Cycle (if enabled).

15.The pump stays on during the pump overrun time (if enabled).

16.At the end of the pump overrun time the pump will be switched off.

LEAD LAG

Burner Control System devices contain the ability to be a stand- alone control, operate as a Lead Lag Master control (which also uses the burner control function as one of the slaves), or to operate solely as a slave to the lead lag system.

Control System devices utilize two ModBus™ ports (MB1 and MB2) for communications. One port is designated to support a system S7999B display and the other port supports communications from the LL Master with its slaves.

The Lead Lag master is a software service that is hosted by a Control System. It is not a part of that control, but is an entity that is “above” all of the individual burner controls (including the one that hosts it). The Lead Lag master sees the controls as a set of Modbus devices, each having certain registers, and in this regard it is entirely a communications bus device, talking to the slave buner controls via Modbus.

The LL master uses a few of the host Buner Control's sensors (header temperature and outdoor temperature) and also the STAT electrical inputs in a configurable way, to provide control information.

LEAD LAG (LL) MASTER GENERAL OPERATION

The XP Boiler is a multiple burner application and it works on the basis of the Lead Lag Operation. The XB Boiler is factory configured for Hydronic/Central Heating application, whereas the XW Boiler is factory configured for Domestic Hot Water application. The LL master coordinates the firing of its slave Control Systems. To do this it adds and drops stages to meet changes in load, and it sends firing rate commands to those that are firing.

The LL master turns the first stage on and eventually turns the last stage off using the same criteria as for any modulation control loop:

When the operating point reaches the Setpoint minus the On hysteresis, then the first Control System is turned on.

When the operating point reaches the Setpoint plus the Off hysteresis then the last slave Control System (or all slave Control Systems) are turned off.

The LL master PID operates using a percent rate: 0% is a request for no heat at all, and 100% means firing at the maximum modulation rate.

This firing rate is sent to the slaves as a percentage, but this is apportioned to the slave Control Systems according to the rate allocation algorithm selected by the Rate allocation method parameter.

For some algorithms, this rate might be common to all slave Control Systems that are firing. For others it might represent the total system capacity and be allocated proportionally.

For example, if there are 4 slaves and the LL master's percent rate is 30%, then it might satisfy this by firing all four slaves at 30%, or by operating the first slave at 80% (20% of the system’s capacity) and a second slave at 40% (10% of the system’s capacity).

The LL master may be aware of slave Control System’s minimum firing rate and use this information for some of its algorithms, but when apportioning rate it may also assign rates that are less than this. In fact, the add-stage and drop-stage algorithms may assume this and be defined in terms of theoretical rates that are possibly lower than the actual minimum rate of the Burner Control System. A Control System that is firing and is being commanded to fire at less than its minimum modulation rate will operate at its minimum rate: this is a standard behavior for a Buner control system in stand-alone (non-slave) mode.

If any slave under LL Master control is in a Run-Limited condition, then for some algorithms the LL master can apportion to that stage the rate that it is actually firing at. Additionally when a slave imposes its own Run-limited rate, this may trigger the LL Master to add a stage, if it needs more capacity, or drop a stage if the run-limiting is providing too much heat (for example if a stage is running at a higher-than commanded rate due to anti- condensation).

By adjusting the parameters in an extreme way it is possible to define add-stage and drop-stage conditions that overlap or even cross over each other. Certainly it is incorrect to do this, and it would take a very deliberate and non-accidental act to accomplish it. But there are two points in this:

1.LL master does not prevent it, and more important;

2.It will not confuse the LL master because it is implemented as a state machine that is in only one state at a time;

48

Page 48
Image 48
A.O. Smith 3400, 2600, 1700, 2000 instruction manual Domestic HOT Water, Lead LAG LL Master General Operation

3400, 1700, 2000, 2600 specifications

A.O. Smith, a leader in water heating solutions, has developed a range of high-efficiency water heaters that cater to various residential and commercial needs. Among their stellar offerings are the A.O. Smith 2600, 2000, 1700, and 3400 models, each boasting impressive features, cutting-edge technologies, and excellent energy efficiency.

The A.O. Smith 2600 model is designed for those who require a robust water heating solution with a capacity to handle high-demand scenarios. It utilizes a highly efficient heating element that provides rapid heating and maintains a steady output. The built-in smart control system allows users to monitor temperature settings and track energy consumption, ensuring optimal performance.

Next in line, the A.O. Smith 2000 is perfect for households that require a reliable and efficient water heater without compromising on space. This compact model integrates advanced thermal insulation that minimizes heat loss, coupled with a powerful heating element that ensures quick heating times. Its sleek design makes it suitable for various installations while maintaining aesthetic appeal.

The A.O. Smith 1700 model caters specifically to smaller residential needs but retains features that align with higher-end models. It incorporates state-of-the-art safety features, including overheat protection and a pressure relief valve. Its lightweight structure and ease of installation stand out, making it a recommended choice for those looking for efficient heating without extensive modifications to their plumbing systems.

Lastly, the A.O. Smith 3400 is a powerhouse designed for larger commercial applications. This model offers exceptional heating capacities and includes advanced technologies such as a digital display for easy monitoring and control. The robust build is complemented by a high-performance insulation system that significantly reduces energy consumption and operating costs.

All A.O. Smith water heaters, including the 2600, 2000, 1700, and 3400 models, feature corrosion-resistant materials ensuring longevity and durability. With their commitment to quality and innovation, A.O. Smith continues to provide water heating solutions that meet modern demands while emphasizing energy efficiency and user convenience. Whether for residential or commercial use, each model represents the pinnacle of reliability and performance in water heating technology.

In conclusion, A.O. Smith has established itself as a reliable choice for water heaters, with models that cater to diverse needs without compromising on efficiency or quality.