and 12" (30.5 cm) from the top. (Standard clearance.) If clearances stated on the heater differ from standard clearances, install water heater according to clearances stated on the heater.

Adequate clearance for servicing this appliance should be considered before installation, such as changing the anodes, etc.

A minimum clearance of 5" (12.7 cm) must be allowed for access to replaceable parts such as the thermostats, drain valve and relief valve.

When installing the heater, consideration must be given to proper location. Location selected should be as close to the wall as practicable and as centralized with the water piping system as possible.

FIGURE 4.

A gas water heater cannot operate properly without the correct amount of air for combustion. Do not install in a confined area such as a closet, unless you provide air as shown in the “Locating The New Water Heater” section. Never obstruct the flow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fire or explosion and cause death, serious bodily injury, or property damage.

FIGURE 5.

If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry cleaning equipment, it is imperative that the water heater or water heaters be installed so that combustion and ventilation air be taken from outside these areas.

Propellants of aerosol sprays and volatile compounds, (cleaners,

chlorine based chemicals, refrigerants, etc.) in addition to being highly flammable in many cases, will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure.

INSULATION BLANKETS

Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. Your water heater meets or exceeds the National Appliance Energy Conversation Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.

Should you choose to apply an insulation blanket to this heater, you should follow these instructions (For identification of components mentioned below, see Figure 1). Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death.

Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood.

Do not cover the outer door, thermostat or temperature & pressure relief valve.

Do not allow insulation to come within 2" (5.1 cm) of the floor to prevent blockage of combustion air flow to the burner.

Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.

Do obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels.

Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow.

COMBUSTION AIR AND VENTILATION FOR APPLIANCES LOCATED IN UNCONFINED SPACES

UNCONFINED SPACE is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in “Combustion Air and Ventilation for Appliances Located in Confined Spaces.”

COMBUSTION AIR AND VENTILATION FOR APPLIANCES LOCATED IN CONFINED SPACES

CONFINED SPACE is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input rating of all appliances installed in that space.

9

Page 9
Image 9
A.O. Smith GPVR-50, GPVX-50, GPVH-50, 315465-000, GPVR-40 Series 102, 185237-004 instruction manual Insulation Blankets

GPVH-50, GPVX-50, GPVR-40 Series 102, GPVR-50, 315465-000 specifications

A.O. Smith is a reputable manufacturer of water heating solutions, and their series of water heaters, particularly models 185237-004, 315465-000, GPVR-50, GPVR-40 Series 102, and GPVX-50, exemplify the company’s commitment to innovation, efficiency, and reliability. These models cater to diverse residential and commercial applications, providing users with versatile options tailored to specific needs.

One of the standout features of these A.O. Smith water heaters is their advanced heating technology. Many of these models, such as the GPVR-50 and GPVR-40 Series 102, are equipped with high-efficiency gas burners designed to maximize thermal efficiency. This ensures that hot water is readily available while minimizing energy consumption, contributing to reduced utility bills.

Additionally, the GPVX-50 model showcases A.O. Smith's investment in Smart Technology. It features a built-in electronic control that allows for precise temperature settings and enhanced system monitoring. This not only optimizes performance but also increases user convenience, making it easier to manage water heating according to personal preferences.

Durability is another core characteristic of these models. The tanks are often constructed from high-quality materials, such as glass-lined steel, which enhances corrosion resistance and extends the lifespan of the unit. Moreover, A.O. Smith incorporates advanced insulation materials that reduce heat loss, maintaining water temperature for longer periods and furthering energy savings.

Safety is paramount in A.O. Smith's designs. Models like the GPVR-50 and GPVX-50 include various safety features, such as automatic shut-off valves and temperature pressure relief valves. These additions ensure that users can operate their water heaters with peace of mind, knowing that safety measures are in place.

Installation flexibility is another significant advantage these models offer. They are designed to fit into various spaces, accommodating different installation requirements, whether it be horizontal or vertical configurations. Such adaptability makes them suitable for various settings, from residential homes to commercial establishments.

In summary, the A.O. Smith 185237-004, 315465-000, GPVR-50, GPVR-40 Series 102, and GPVX-50 water heaters offer a range of advanced features, technologies, and characteristics designed to enhance efficiency, reliability, and user experience. With a focus on innovation, safety, and durability, these products stand as a testament to A.O. Smith's commitment to delivering high-quality water heating solutions for consumers everywhere.