ENGLISH
12
Installation
3.2.3 Control terminalsTerminal Data for control connections
1Digital Input: Start/Stop input resistance = 4.3kΩ
2Analog Common
5Analog Input: 0...10 VDC input resistance: >50 kΩ
6Internal DC supply for speed pot +10 VDC, max. 10 mA
25 Analog Input: 4...20 mA input resistance: 250Ω
4Digital Reference/Common +15 VDC / 0 VDC, depending on assertion level
11 Internal DC supply for external devices +12 VDC, max. 50 mA
13A Digital Input: Configurable with P121
input resistance = 4.3kΩ
13B Digital Input: Configurable with P122
13C Digital Input: Configurable with P123
14 Digital Output: Configurable with P142 DC 24 V / 50 mA; NPN
30 Analog Output: Configurable with P150…P155 0…10 VDC, max. 20 mA
16 Relay output: Configurable with P140 AC 250 V / 3 A
DC 24 V / 2 A … 240 V / 0.22 A, non-inductive
17
6 25 4 11
13A
13B
13C
17
51 2 14 30
16
AOUT
DIGOUT
2k … 10k
+10 V
AIN
AIN
COM
COM
ALsw
252
4 … 20 mA
52
0 … 10 V
0 … 5 V
1 2 4
13A
13B
13C
+12 VDC - 0 %
…
+30 VDC + 0 %
ALsw
+15V
1 2 4
13A
13B
13C
ALsw
COM
PNP NPN
4.5 lb-in
(0.5 Nm)
0.25 in (6 mm)
AWG 26…16
(<1mm²)
V0109
Assertion level of digital inputs
The digital inputs can be configured for active-high or active-low by setting the Assertion Level
Switch (ALsw) and P120. If wiring to the drive inputs with dry contacts or with PNP solid state
switches, set the switch and P120 to “High” (+). If using NPN devices for inputs, set both to “Low”
(-). Active-high (+) is the default setting.
HIGH = +12 … +30 V
LOW = 0 … +3 V
Note