Commissioning
Code Possible Settings IMPORTANT
No. Name Default Selection
Relay Output
TB-16, 17
0 0 None Disables the output
1 Run Energizes when the drive is running
2 Reverse Energizes when reverse rotation is active
3 Fault De-energizes when the drive trips, or
power is removed
4 Inverse Fault Energizes when the drive trips
5 Fault Lockout P110 = 3...6: De-energizes if all restart
attempts fail
6 At Speed Energizes when output frequency =
commanded frequency
7 Above Preset Speed #6 Energizes when output freq. > P136
8 Current Limit Energizes when motor current = P171
9 Follower Loss (4-20 mA) Energizes when 4-20 mA signal falls
below 2 mA
10 Loss of Load Energizes when motor load drops
below P145; see also P146
11 Local Keypad Control Active
Energizes when the selected source is
active for start control
12 Terminal Strip Control Active
13 Remote Keypad Control Active
14 Network Control Active
15 Standard Reference Active Energizes when P101 reference is active
16 Auto Reference Active Energizes when Auto Reference
is activated using TB-13 input; see
P121...P123
17 Sleep Mode Active See P240...P242
18 PID Feedback < Min. Alarm Energizes when PID feedback signal
< P214
19 Inverse PID Feedback < Min.
Alarm
De-energizes when PID feedback
signal < P214
20 PID Feedback > Max Alarm Energizes when PID feedback
signal > P215
21 Inverse PID Feedback > Max
Alarm
De-energizes when PID feedback
signal > P215
22 PID Feedback within
Min/Max Alarm range
Energizes when PID feedback signal
is within the Min/Max Alarm range; see
P214, P215
23 PID Feedback outside
Min/Max Alarm range
Energizes when PID feedback signal is
outside the Min/Max Alarm range; see
P214, P215
24 Reserved
25 Network Activated Requires optional communication
module (refer to the network module
documentation).