Commissioning
4.5 Parameter menu

4.5.1 Basic Setup Parameters

Code Possible Settings IMPORTANT
No. Name Default Selection
Start Control
Source
0 0 Local Keypad Use RUN button on front of drive to start
1 Terminal Strip Use start/stop circuit wired into the
terminal strip. See Section 3.2.3
2 Remote Keypad Only Use RUN button on optional Remote
Keypad to start
3 Network Only Start command must come from
network (Modbus, CANopen, etc)
• Requires optional communication
module (refer to the network module
documentation).
• Must also set one of the TB-13
inputs to 9 (Network Enable); see
P121...P123
4 Terminal Strip or Local
Keypad
Allows start control to be switched
between terminal strip and local
keypad using one of the TB-13 inputs.
See note below.
5 Terminal Strip or Remote
Keypad
Allows start control to be switched
between terminal strip and optional
remote keypad using one of the TB-13
inputs. See note below.
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be disabled
if parameters are reset back to defaults (see P199)
Note
• P100 = 4, 5: To switch between control sources, one of the TB-13
inputs (P121...P123) must be set to 08 (Control Select);
TB-13x OPEN (or not configured): Terminal strip control
TB-13x CLOSED: Local (P100 = 4) or Remote (P100 = 5) keypad
• P100 = 0, 1, 4: Network can take control if P121...P123 = 9 and the
corresponding TB-13x input is CLOSED.
• The STOP button on the front of the drive is always active except in
JOG mode.
An fault will occur if the Assertion Level switch (ALsw)
position does not match the P120 setting and P100 is set to a
value other than 0.
Standard
Reference
Source
0 0 Keypad (Local or Remote) Selects the default speed or torque
reference when no Auto Reference is
selected using the TB-13 inputs
1 0-10 VDC
2 4-20 mA
3 Preset #1
4 Preset #2
5 Preset #3
6 Network