ADCP-80-524 • Issue 1 • November 2001

Caution: When attaching the cable management bar to the fuse panel, use only the hardware supplied with the cable management bar. Use of any other hardware could cause contact with internal parts of the fuse panel. If parts are missing, please contact ADC.

Note: A fuse panel with the cable management bar attached may exceed the 12-inch (3.05 mm) overall depth objective described in GR-63 CORE, 02-14.

MOUNTING BRACKET

INSTALLED FOR

19-IN. (48.26 CM)

RACK MOUNTING

ATTACH TO

EITHER SET

OF 3 HOLES

CABLE

 

MANAGEMENT

16387-B

BAR

 

Figure 15. Cable Management Bar Installation (Uninterrupted Power Fuse Panel Shown)

4.5Rack Mounting

The fuse panel can be mounted in either a 19- or 23-inch (48.26 or 58.42 cm) wide rack. Two sets of mounting brackets, one set for 19-inch racks and one set for 23-inch racks, are provided with the fuse panel. Eight 5/16-inch (7.94 mm) long, thread-forming, Phillips-drive, 8-32 flat- head screws are provided for attaching the mounting brackets to the panel. Four 3/8-inch (9.53

mm)long, Phillips-drive, 12-24 pan-head screws (with #12 flat washers) are provided for attaching the mounting brackets to the equipment rack.

Caution: When attaching the mounting brackets to the fuse panel, use only the 5/16-inch (7.94

mm)long, black chromate finish, thread forming, flathead screws provided with the panel. Use of any other hardware could cause contact with internal parts of the panel. If parts are missing, contact ADC to order replacement parts.

Use the following procedure to install the fuse panel in the equipment rack:

1.Select the set of mounting brackets (19- or 23-inch) that correspond to the width of the equipment rack into which the fuse panel will be installed.

2.Orient the mounting brackets as shown in Figure 16.

3.Attach the brackets to the sides of the fuse panel chassis using the eight 5/16-inch (7.94

mm)flathead screws provided. Tighten screws to 15 pound force-inches (1.7 Newton meters) of torque to insure grounding.

4.Place the fuse panel in the specified mounting space within the rack.

5.Secure the panel to the rack as shown in Figure 17 using the four 3/8-inch (9.525 mm) long pan-head screws and flat washers provided.

Page 22