Standard Equipment
Type 70 series fuse panels have two power buses (feeds). The capacity of each bus is eight fuse positions with up to 10 Amps per fuse position (within the maximum bus capacity). Each bus has
The current capacity of each bus of the traditional power fuse panel is 65 Amps maximum (130 Amps per panel). The current capacity of each bus of the uninterrupted power fuse panel is 60 Amps maximum (60 Amps per panel).
The power dissipation of each fuse panel is 40 watts maximum at 130 Amps.
The dimensions of each fuse panel are 1.75 inches (4.45 centimeters) high, 17.13 inches (43.51 centimeters) wide, and 10.01 inches (25.42 centimeters) deep (does not include depth of protective cover and connectors, fuses, and visual indicators that extend beyond the chassis.
Two sets of mounting brackets are provided with each fuse panel, one set for
A typical traditional power fuse panel with protective cover in place is shown in Figure 1. A typical uninterrupted power fuse panel with protective cover in place is shown in Figure 2.
Fuse panels are shipped without fuses. The required fuses are available separately as accessory items.
Options
All fuse panels are available with the following options:
•Two types of output connectors:
•Two types of input connectors are available:
•The fuse panel color is either putty white or black color
Accessories
The following accessories are available:
•Standard type 70 fuses with standard values from 0.2 Amp to 10.0 Amps
•Cable management bar kit
•Four sizes of compression connector lugs for input power connections
•Fused equipment designation card kit
•Fuse designation card kit