3URGXFW'HVFULSWLRQ ,QYHQWRU\
 8QLPRGH31&
SECTION 1 Product Description
The ADT Unimode 9600 is a compact, cost effective, intelligent addressable FACP (Fire
Alarm Control Panel) with an extensive list of powerful features. The combination of
newer series devices and legacy 300 Series devices, along with the Unimode 9600 FACP,
offer the latest in fire protection technology. The power supply and all electronics are
contained on a single circuit board housed in a metal cabinet, providing a complete fire
control system for most applications. Optional modules, which plug into the main circuit
board, are available for special functions. Available accessories include LED, graphic and
LCD annunciators, reverse polarity/city box transmitter, digital alarm communicator/
transmitter, SLC expansion module, local and remote upload/download software and
remote power expansion.
1.1 Inventory
When the Unimode 9600 shipment is received, check to make certain that all parts have
been included in the shipment. The Unimode 9600 shipment should consist of one of each
of the following:
main circuit board with display
backbox with door
plastic bag containing screws, cables, key, etc.
manual
1.2 Features and Options
Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7
requirements
Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7
requirements
318 addressable device capacity for each SLC loop (159 detectors and 159 control/
monitor modules)
99 software zones
Two onboard NACs (Notification Appliance Circuits) with additional NAC
capability using control modules
6.0 amps total power for NACs and 24 VDC auxiliary power outputs
7.2 amps total system power (includes battery charger)
Two programmable relay outputs and one fixed trouble relay
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible