Master Programming Level Programming
Unimode 9600 PN 51336:C 11/06/01 83
3.6.4.5.2 Type
The main circuit board NAC type can be programmed by pressing 2 while viewing
NAC Screen #1. The following screens will be displayed:
Select the NAC device type by pressing the number corresponding to the type in the
appropriate screen as shown above. When the selection is made, the display will
return to NAC Screen #1.
The following table contains NAC type codes and their functions:
3.6.4.5.3 Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to
Silenceable No. This will prevent the selected main circuit board NAC from being
silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each press
of the 3 key will cause the display to toggle between Silenceable Yes and Silenceable
No.
Important: When a Notification Appliance Circuit with a mix of audible and visual
devices is programmed for silenceable and the synchronization feature is selected,
only the audible devices will be turned off if the Silence key is pressed. The visual
devices (strobes, etc.) will continue to operate.
NAC Type Code Special Function
Bell None
Horn None
Strobe None
Synced Strobe Synchronized to manufacturer
Audible None
Siren Circuit None
Blank None
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
@@@@@@@NAC@TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1
@@@@@@@NAC@TYPE
1=FUTURE
2=SIREN CIRCUIT
3=BLANK
Type Screen #2
@@@@@@@NAC@TYPE
1=SYNCED@STROBE
2=FUTURE
3=AUDIBLE
Type Screen #3