Master Programming Level Programming
Unimode 9600 PN 51336:C 11/06/01 73
3.6.2.7 Zone Type
Zone Types must be programmed only if a DACT, programmed for zone reporting, is
installed on the control panel. Pressing 1 for Zone Types, while viewing Zone Setup
Screen #3, will display a screen similar to the following:
This display will show the system zones (default and user programmed) and their
associated types. Note that an up and/or down arrow will appear in the upper right
corner of the display, indicating that additional screens of zone information exists.
Press the up or down arrow keys to view zones Z00 through Z99.
Zone types can be changed by pressing the keypad number key corresponding to the
zone in each Zones Installed Screen. Available zone types will be displayed in the
resultant screens. For example, to change the zone type for zone Z02 in the screen
illustrated above, press 3. The following screens will be displayed:
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type
Program Screen #2 is displayed. Press 2 to program zone Z02 as a Pull Station zone.
The display will return to the Zones Installed Screen showing zone Z02 and the Pull
Station program type. Repeat the procedure for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign
a Waterflow silenceable zone type to the selected zone. Any signaling devices
programmed to the same zone can be silenced by pressing the Alarm Silence key or by
using the auto-silence feature.
To program a waterflow circuit as nonsilenceable, connect the waterflow device(s) to a
monitor module programmed as a Waterflow device (see "Edit Module Screen for
Monitor Module" on page 54) and assign the module to a particular zone. Program a
control module as nonsilenceable (see "Edit Module Screen for Control Modules" on
page 63) and assign it to the same zone as the waterflow type monitor module. All
notification appliances connected to the control module will be nonsilenceable as will
any other devices assigned to the same zone.
ZONE SETUP
1=ZONE TYPES
Zone Setup Screen #3
@@ZONE@TYPE@PROG
1=Z00@@ALARM
2=Z01@@ALARM
3=Z02@@ALARM
Zones Installed Screen
@@ZONE@TYPE@PROG
1=ALARM
2=SMOKE
3=WATERFLOW
Zone Type Program Screen #1
@@ZONE@TYPE@PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #3
@@ZONE@TYPE@PROG
1=SUPERVISORY
2=PROC.@MON
3=VOICE@EVAC
Zone Type Program Screen #4
@@ZONE@TYPE@PROG
1=HEAT
2=PULL@STATION
3=DUCT
Zone Type Program Screen #2