3

Classification VFI SS 111 acc. to IEC 62040-3

 

 

Protect 3.M 2.0

 

 

Power type rating

20 kVA

40 kVA

60 kVA

80 kVA

100 kVA

120 kVA

 

 

 

 

 

 

 

 

16 kW

32 kW

48 kW

64 kW

80 kW

96 kW

System

 

 

 

 

 

 

Nominal input current

29 A

59 A

88 A

117 A

145 A

172 A

 

 

 

 

 

 

 

Efficiency (typical)

 

 

 

95 %

 

 

Efficiency in ECO mode

 

 

 

98 %

 

 

Waste heat from power (typical)

1.3 kW

2.6 kW

3.9 kW

5.2 kW

6.5 kW

7.8 kW

 

 

 

 

 

 

 

 

4436 BTU/h

8872 BTU/h

13308 BTU/h

17744 BTU/h

22180 BTU/h

26616 BTU/h

 

 

 

 

 

 

 

Airflow (max.) m³/h

309

617

926

1234

1543

1852

Input

 

 

 

 

 

 

Nominal voltage

 

3 x 400 V (380 V, 415 V adjustable), 3 phase + neutral

 

 

 

 

 

 

 

Input voltage range

 

 

305 – 477 V

 

 

 

 

 

 

 

 

Frequency

 

 

50 Hz/ 60 Hz (adjustable)

 

 

Total harmonic distortion (THDv)

 

 

≤3 % 1)

 

 

 

 

 

 

 

 

 

Power factor

 

 

 

>0.99

 

 

Inverter

 

 

 

 

 

 

Nominal voltage

 

3 x 400 V (380 V, 415 V adjustable), 3 phase + neutral

 

 

 

 

 

 

 

Frequency

 

 

50 / 60 Hz (adjustable)

 

 

 

 

 

 

 

 

Precision static /dynamic

 

 

±1 % / ±7 %

 

 

 

 

 

 

 

 

Total harmonic distortion (THDv)

 

 

<3 % ( linear load), <5 % (non-linear load)

 

 

 

 

 

 

Max. phase displacement

 

±1.5 % (balanced load), ±2 % (100 % unbalanced load)

 

Admissible overload

 

 

125 % for 10 min., 150 % for 60 s

 

 

 

 

 

 

 

 

 

Crest factor

 

 

 

2.7 : 1

 

 

 

 

 

 

 

 

Max. short circuit current

 

 

>270 % of the rated current

 

 

 

 

 

 

 

 

Admissible power factor

 

 

0.1 inductive to 0.1 capacitive

 

 

Battery

 

 

 

 

 

 

Rated voltage

 

 

±240 V DC

 

 

 

 

 

 

 

 

 

Max. charging power

5 A

10 A

15 A

20 A

25 A

30 A

 

 

 

 

 

 

Charging principle

 

 

Load switching per power module

 

 

Autonomy time

 

 

Selectable over external battery cabinet

 

 

Static bypass

 

 

 

 

 

 

Nominal voltage

 

3 x 400 V (380, 415 V adjustable), 3 phase + neutral

 

 

 

 

 

 

 

Frequency

 

 

50 Hz / 60 Hz (adjustable)

 

 

 

 

 

 

 

 

Synchronization range

 

 

±0.1 – ±5 % (adjustable)

 

 

 

 

 

 

 

 

Transfer time at mains outage

 

 

0 ms (without interruption)

 

 

 

 

 

 

 

 

Admissible overload

 

 

175 % for 10 ms

 

 

General data

 

 

 

 

 

 

Parallel mode

 

 

Up to 4 UPS (central battery possible)

 

 

 

 

 

 

Audible noise

 

62 – 69 dB(A) dependent on equipment installed and load state

 

 

 

 

 

 

 

Operating temperature range / humidity

 

 

0 – 40 °C / <95 % (without condensation)

 

 

 

 

 

 

 

 

 

Protection

 

 

 

IP20

 

 

 

 

 

 

 

 

Color

 

 

RAL 7035

 

 

 

 

 

 

 

 

Cable entry

 

 

Underside

 

 

 

 

 

 

 

 

Environmental conditions

 

 

Free from corrosive air and conductive dust

 

 

Communication

 

 

 

 

 

 

Display

 

 

320 x 240 graphical LCD display

 

 

 

 

 

 

 

 

Alarm signals

 

 

Acoustic and visual

 

 

 

 

Interfaces

Remote signal contact, RS232, 2 x communication slots for SNMP / Modbus / additional relay cards

Dimensions

 

 

 

 

 

 

Dimensions approx. D x W x H (mm)

 

910 x 520 x 1165

 

975 x 520 x 1655

 

 

 

 

 

 

 

Footprint (m²)

 

 

0.47

 

 

0.51

 

 

 

 

 

 

 

Weight approx.

 

 

139 kg

 

 

204 kg

Weight approx. (incl. module)

169 kg

199 kg

229 kg

259 kg

354 kg

384 kg

1) by THDv ≤2 %

 

 

 

 

 

 

Page 3
Image 3
AEG 3.M 2 manual By THDv ≤2 %