Note that the additional output socket identified

in white has a special property (chapter 4.3 / no.

6 / pg.19).

 

This is always live irrespective of the other

 

outputs. It is not backed up by the UPS, nor can

 

it be switched off using the main switch of the

 

UPS. It is intended for loads that should be

 

protected against overvoltage but do not

 

necessarily need a continued power supply

 

(emergency power) in case of a mains failure.

 

Limit the power to max. 500 W.

5.5Modem/Phone Connection (data line protection)

Connect the incoming phone line into the “IN” connection on the back of the PROTECT A.

Connect the data terminal unit (phone, fax, modem) to the “OUT” socket.

The data line protection has been designed for i RJ11 and does not support network cables (RJ45); these should be protected by external

measures if necessary.

Data lines are not supplied with the UPS.

5.6Communication Connection, Connection with USB or Serial Cable

In order to allow unsupervised shutdown of the operating system, connect the RS232 or USB cable as shown in the drawing.

The USB connection is automatically detected.

22