6 Displays and Troubleshooting

6.1Warning Sounds

Warning

Meaning

sound

 

 

 

Sounds every 10

UPS is operating in battery mode.

seconds

 

 

 

Sounds every

UPS is running in battery mode and will shortly

second

shut down (battery system has reached the battery

 

undervoltage limit).

 

 

Sounds every two

Battery system faulty, it may have to be renewed

seconds

(battery diagnosis negative).

 

 

Sounds twice every

UPS output is overloaded.

second

 

 

 

Sounds every 2

Overload of the step-up/down converter due to

seconds;

UPS overload.

continuous warning

 

sound after 50 min

 

 

 

Sustained warning

UPS faulty.

sound

 

 

 

6.2General Troubleshooting and Fault Rectification

Fault

Cause

Solution

 

 

 

No LED display on

Battery missing

Insert the battery and first

the front cover plate

 

charge it up for at least 8 hours

 

 

 

 

Battery fault

Renew the battery with a

 

 

battery of the same type

 

 

 

 

On/off switch not pressed

Press the switch again

 

 

 

Alarm buzzer sounds

UPS overload

Check whether the load

continuously with

 

matches the UPS capacity

normal AC supply

 

indicated in the technical

 

 

data

 

 

 