WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
Electrical Speciî‚¿cations HF304, IHF304, IHF075, CHF304, CHF075304 liters / 75 pounds
Boiler Fed/Steam Heat Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full Load Amps
Recommended
Circuit Breaker (US-
market)
AWG/mm2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 16 20 20 12/4.0
6x3 kW
42 50 50 8/10.0
P 380-415 50/60 3 3+N+PE 25 30 32 10/6.0 51 60 60 6/16.0
Q 200-240 50/60 3 3+PE 25 30 32 10/6.0 71 80 80 4/25.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A N/A N/A N/A N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
3x3 kW +
3x4 kW
46 50 50 8/10.0
P 380-415 50/60 3 3+N+PE 56 60 60 6/16.0
Q 200-240 50/60 3 3+PE N/A N/A N/A N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
6x4 kW
51 60 60 6/16.0
P 380-415 50/60 3 3+N+PE 60 70 70 4/25.0
Q 200-240 50/60 3 3+PE N/A N/A N/A N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
3x6 kW +
3x4 kW
59 70 70 4/25.0
P 380-415 50/60 3 3+N+PE 69 80 80 4/25.0
Q 200-240 50/60 3 3+PE N/A N/A N/A N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
Table 6