WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
Electrical Speciî‚¿cations WF150, IWF150, IWF033, CWF033150 liters / 33 pounds
Boiler Fed/Steam Heat Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full Load Amps
Recommended
Circuit Breaker (US-
market)
AWG/mm2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 4 10 10 14/2.5
6x3 kW
30 40 40 8/10.0
P 380-415 50/60 3 3+N+PE 12 15 16 14/2.5 38 50 50 8/10.0
Q200-240 50/60 3 3+PE 12 15 16 14/2.5 57 70 70 4/25.0
X 200-240 50/60 1/3 2/3+PE 12 15 16 14/2.5 N/A N/A N/A N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
3x3 kW +
3x2 kW
26 30 30 10/6.0
P 380-415 50/60 3 3+N+PE 34 40 40 8/10.0
Q200-240 50/60 3 3+PE 50 60 60 6/16.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
3x3 kW +
3x4 kW
34 40 40 8/10.0
P 380-415 50/60 3 3+N+PE 53 60 60 6/16.0
Q200-240 50/60 3 3+PE N/A N/A N/A N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
6x2 kW
21 30 30 10/6.0
P 380-415 50/60 3 3+N+PE 30 40 40 8/10.0
Q200-240 50/60 3 3+PE 42 50 50 8/10.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
6x4 kW
39 50 50 8/10.0
P 380-415 50/60 3 3+N+PE 47 60 60 6/16.0
Q200-240 50/60 3 3+PE N/A N/A N/A N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
Table 3