4

WARNING

The washer-extractor should be connected to an individual branch circuit not shared with lighting or other equipment.

Electrical Specifications WF235, IWF235, IWF055, CWF235, CWF055

235 liters / 55 pounds

 

 

 

 

 

Boiler Fed/Steam Heat

 

Electric Heat

 

Code

Voltage

Cycle

Phase

Wire

Full Load Amps

 

Recommended Circuit Breaker (US-market)

AWG/mm2

kW Standard Heating Elements

Full Load Amps

 

Recommended Circuit Breaker (US- market)

AWG/mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

US

NON-US

 

 

 

US

 

NON-US

 

N

440-480

50/60

3

3+PE

6

15

10

14/2.5

 

32

40

 

40

8/10.0

P

380-415

50/60

3

3+N+PE

16

20

20

12/4.0

6x3 kW

43

50

 

50

8/10.0

Q

200-240

50/60

3

3+PE

16

20

20

12/4.0

62

70

 

70

4/25.0

 

 

X

200-240

50/60

1/3

2/3+PE

16

20

20

12/4.0

 

N/A

N/A

 

N/A

N/A

 

 

 

 

 

 

 

 

 

Alternative Electric Heat Options

N

440-480

50/60

3

3+PE

 

 

 

 

 

27

30

 

32

10/6.0

P

380-415

50/60

3

3+N+PE

 

 

 

 

3x3 kW +

40

50

 

50

8/10.0

Q

200-240

50/60

3

3+PE

 

 

 

 

3x2 kW

56

60

 

60

6/16.0

X

200-240

50/60

1/3

2/3+PE

 

 

 

 

 

N/A

N/A

 

N/A

N/A

N

440-480

50/60

3

3+PE

 

 

 

 

 

36

40

 

40

8/10.0

P

380-415

50/60

3

3+N+PE

 

 

 

 

3x3 kW +

48

50

 

50

8/10.0

Q

200-240

50/60

3

3+PE

 

 

 

 

3x4 kW

N/A

N/A

 

N/A

N/A

X

200-240

50/60

1/3

2/3+PE

 

 

 

 

 

N/A

N/A

 

N/A

N/A

N

440-480

50/60

3

3+PE

 

 

 

 

 

23

30

 

25

10/6.0

P

380-415

50/60

3

3+N+PE

 

 

 

 

6x2 kW

35

40

 

40

8/10.0

Q

200-240

50/60

3

3+PE

 

 

 

 

48

50

 

50

8/10.0

 

 

 

 

 

 

X

200-240

50/60

1/3

2/3+PE

 

 

 

 

 

N/A

N/A

 

N/A

N/A

N

440-480

50/60

3

3+PE

 

 

 

 

 

40

50

 

50

8/10.0

P

380-415

50/60

3

3+N+PE

 

 

 

 

6x4 kW

53

60

 

60

8/10.0

Q

200-240

50/60

3

3+PE

 

 

 

 

N/A

N/A

 

N/A

N/A

 

 

 

 

 

 

X

200-240

50/60

1/3

2/3+PE

 

 

 

 

 

N/A

N/A

 

N/A

N/A

 

 

 

 

 

 

 

Table 5

 

 

 

 

 

 

 