CO RRECTIVE MAINTENANCE TROUBLE S HOOTING GUIDE
|
|
|
|
SYMPTOMS |
| POSSIBLE FAILURE | |
|
|
|
|
Unit does not cool. | ∙ | Bad connection at supply | |
|
| cord. | |
| ∙ | ||
| ∙ | Low refrigerant. | |
|
|
| |
Unit does not operate. | ∙ | Control failure. |
|
| ∙ | Incorrect voltage. | |
| ∙ Bad connection at supply | ||
| ∙ | cord. | |
| Failed compressor. | ||
Unit runs continuously. | ∙ | Low on Refrigera | nt. |
| ∙ | Control failure. | |
| ∙ Restricted air flow or | ||
| ∙ | dirty condenser coil. | |
| Bad condenser fan | ||
|
| motor. | |
| ∙ | Compressor failure. | |
| ∙ Ineffective door seal. | ||
| ∙ Air circulation in storage | ||
|
| restricted. |
|
Low head pressure. | ∙ | Defective compressor. | |
| ∙ | Low refrigerant. | |
| ∙ Ambient temperature too | ||
|
| low. | |
High head pressure. | ∙ | Blocked or dirty |
|
|
| condenser. | |
| ∙ Ambient temperature too | ||
|
| high. | |
| ∙ | System contains air. | |
| ∙ | Refrigerant overcharge. | |
|
|
|
|
Short cycling. | ∙ | ||
|
|
|
|
SOLUTION
∙Check supply cord at outlet.
∙Tighten strike on door latch.
∙Check system for leaks and recharge.
∙Adjust control or replace.
∙Supply correct voltage.
∙Replace or repair.
∙Replace.
∙
∙Adjust control or replace.
∙Rectify air flow problem and clean condenser.
∙Check and replace if necessary.
∙Replace.
∙Adjust door strike.
∙Redistribute food and even air flow.
∙Replace.
∙Leak check system and recharge.
∙Redistribute food for even air flow.
∙Clean and remove any obstructions.
∙Improve room temperature.
∙Evacuate, change the filter dryer and recharge.
∙Reduce refrigerant in the system.
∙Adjust control.
This chart is provided for the assistance of qualified technicians only and is not intended for use by untrained or unauthorized service personnel.