Amcor WV-100, WV 50, WV 150 owner manual TEST Key, Temperature Settings

Models: WV 150 WV-100 WV 50

1 34
Download 34 pages 22.21 Kb
Page 10
Image 10
TEST Key:

Temperature Settings

TEST Key:

If this Key is pressed in Standby state, the compressor and electric heating device will operate at the same time, and Compressor Indicator LED and Electric Heating Indicator LED will come on at the same time. When this key is released, the system returns to previous standby state.

This key is invalid in operational state.

Notes:

1.There should be at least 5-minute interval between compressor stopping and starting again.

The compressor should operate for at least five minutes after it is started up and then its operation can be stopped depending on actual conditions.

2.The temperature indicating range of Digital Display 1 and Digital Display 2 is 32°F - 99°F.

When the temperature is below 32ºF in the storage cabinet, indicated temperature is 000, and when the ambient temperature is above 99°F in the storage cabinet, the indicated temperature is 99°F.

3.The difference of temperature displayed on Digital Display 1 and Digital Display 2 should be above 41°F.

4.The temperature setting range of upper layer (54°F - 72°F) and lower layer (41°F - 54°F) are effective when the ambient temperature is 90°F, otherwise it would be difficult to reach the lowest setting temperature of upper layer and lower layer.

5.The difference between display temperature and setting temperature is ±3°F, when the cabinet temperature is balanced.

8

Page 10
Image 10
Amcor WV-100, WV 50, WV 150 owner manual TEST Key, Temperature Settings