Dealer Installation Instructions
Forced air handler/furnace system with an HRV/ERV
This application provides filtration of all Outdoor Air (OA) that is brought into the home through the HRV/ERV, thus reducing the introduction of dust, pollen and mold from the outdoor air. For systems that have HRV/ERV units installed, we recommend ducting the ‘fresh air’ outflow from the HRV/ERV into the HEPA system. If the HRV/ERV CFM (cubic feet per minute) rating is lower than that of the HEPA system, an additional return needs to be installed into the HEPA system (See figure 8.) The outflow air from the HEPA system then needs to be installed into the main return of the air handler/furnace system. Ensure that you follow the proper installation instructions as outlined in the HRV/ERV Installation manual(s).
Preparation: |
| Example of Return to | |
| Return Installation | ||
Here are some things to consider as you |
| ||
| with an HRV/ERV | ||
decide where to install the HEPA system | HRV/ERV | ||
For homes with a forced | |||
with an HRV/ERV. |
| ||
| air handler/furnace sys- | ||
|
| ||
Location: |
| tem and an HRV/ERV | |
| system. | ||
• Make sure there is room to open the |
| ||
| Additional Return | ||
HEPA filter access panel for filter |
| ||
changes/inspections. |
| Air Handler/Furnace | |
• Keep the HEPA system in a location |
| Air Handler/Furnace Filter | |
where you can still access the air han- |
| HEPA System | |
dler/furnace filter. |
| Figure 16. | |
|
| ||
• Keep the HEPA system away from | NOTE: This filtration system is an ADDITIONAL filter, and does NOT | ||
possible water damage | replace the existing air handler/furnace system filter. |
• Vibration pads will reduce vibration for |
|
|
|
|
|
|
| ble (if the duct runs are too long, reduced CFM |
| ||
installations where the unit is placed on the floor. |
|
| |||
• Install HEPA System on floor or suspended platform. |
| may result). |
|
| |
If the unit is suspended, screws must not penetrate |
| • If duct is exposed to unconditioned air, externally |
| ||
through the cabinet. Make sure that you have the |
| insulated flex duct is highly recommended. |
| ||
proper chains/straps/joists and equipment to keep |
| • Externally insulated flex duct can also be used for |
| ||
unit secure. |
| noise reduction purposes. |
|
| |
Intake (Marked as ‘Air In’ on unit): |
| • For best indoor air quality, do not use ductboard or |
| ||
• Most HRV/ERV systems will not move as much air |
| fiberglass inside of ducts. |
|
| |
as the HEPA system. For these systems, install an |
| Electricity: |
|
| |
additional return from another treated air source |
| • The unit must be plugged into a grounded 120V, |
| ||
into the HEPA system. |
| 60Hz outlet. |
|
| |
• If using an additional return duct, it should be |
| Required Materials for Installation of Unit: |
| ||
installed upstream of any humidifiers. The fresh |
|
| |||
air outflow of the HRV/ERV should be "Y" connect- |
| Items for 2500HV & 4000HV |
|
| |
ed to the additional return duct then connected to |
| Flex or rigid duct | 6” round |
| |
the inlet of the HEPA system. |
| (length as required) |
|
| |
• The additional return duct (if any) should be |
| Takeoffs | Two 6” |
| |
installed at least 6 ft. away from the outflow duct |
| Items for 6000V |
|
| |
on the main return. |
| Flex or rigid duct | 10” round & 8” round |
| |
• Duct both the HRV/ERV and the additional return |
| (length as required) |
|
| |
into the intake of the HEPA system. |
| Takeoffs | One 10” & One 8” |
| |
Outflow (Marked as ‘Clean Air Out’ on unit): |
| Items for 6500, 8500 & 10000 |
|
| |
|
|
| Flex or rigid duct | 12” round or 10” x 12” |
|
• Outflow duct should be installed as close to the air |
| ||||
handler/furnace inlet as possible but not directly |
| (length as required) |
|
| |
into the return air elbow of the main return. |
| Takeoffs | Two 10”x12” |
| |
Ducting: |
| All Models |
|
| |
|
|
| Aluminum tape or mastic as required |
| |
• If HEPA system is installed where inlet and outflow |
| ||||
collars face down, metal elbows must be connected |
| Misc. hanging materials - field provided |
| ||
to both inlet and outflow collars. |
| NOTE: Be sure to review ‘Rules for Safe Installation |
| ||
• Each connection must be sealed with aluminum |
| and Operation’ on page 1 of this document before |
| ||
tape or mastic, including all take offs. |
|
|
|
|
• Installed duct runs should be as straight as possi-
10