Americair 8500 & 10000 and Operation’ on page 1 of this document before, start-upof this unit

Models: 2500HV 6000V 8500 & 10000 6500 4000HV

1 16
Download 16 pages 25.47 Kb
Page 10
Image 10
and Operation’ on page 1 of this document before

Dealer Installation Instructions

Forced air handler/furnace system with an HRV/ERV

This application provides filtration of all Outdoor Air (OA) that is brought into the home through the HRV/ERV, thus reducing the introduction of dust, pollen and mold from the outdoor air. For systems that have HRV/ERV units installed, we recommend ducting the ‘fresh air’ outflow from the HRV/ERV into the HEPA system. If the HRV/ERV CFM (cubic feet per minute) rating is lower than that of the HEPA system, an additional return needs to be installed into the HEPA system (See figure 8.) The outflow air from the HEPA system then needs to be installed into the main return of the air handler/furnace system. Ensure that you follow the proper installation instructions as outlined in the HRV/ERV Installation manual(s).

Preparation:

 

Example of Return to

 

Return Installation

Here are some things to consider as you

 

 

with an HRV/ERV

decide where to install the HEPA system

HRV/ERV

For homes with a forced

with an HRV/ERV.

 

 

air handler/furnace sys-

 

 

Location:

 

tem and an HRV/ERV

 

system.

• Make sure there is room to open the

 

 

Additional Return

HEPA filter access panel for filter

 

changes/inspections.

 

Air Handler/Furnace

• Keep the HEPA system in a location

 

Air Handler/Furnace Filter

where you can still access the air han-

 

HEPA System

dler/furnace filter.

 

Figure 16.

 

 

• Keep the HEPA system away from

NOTE: This filtration system is an ADDITIONAL filter, and does NOT

possible water damage

replace the existing air handler/furnace system filter.

• Vibration pads will reduce vibration for

 

 

 

 

 

 

 

ble (if the duct runs are too long, reduced CFM

 

installations where the unit is placed on the floor.

 

 

• Install HEPA System on floor or suspended platform.

 

may result).

 

 

If the unit is suspended, screws must not penetrate

 

• If duct is exposed to unconditioned air, externally

 

through the cabinet. Make sure that you have the

 

insulated flex duct is highly recommended.

 

proper chains/straps/joists and equipment to keep

 

• Externally insulated flex duct can also be used for

 

unit secure.

 

noise reduction purposes.

 

 

Intake (Marked as ‘Air In’ on unit):

 

• For best indoor air quality, do not use ductboard or

 

• Most HRV/ERV systems will not move as much air

 

fiberglass inside of ducts.

 

 

as the HEPA system. For these systems, install an

 

Electricity:

 

 

additional return from another treated air source

 

• The unit must be plugged into a grounded 120V,

 

into the HEPA system.

 

60Hz outlet.

 

 

• If using an additional return duct, it should be

 

Required Materials for Installation of Unit:

 

installed upstream of any humidifiers. The fresh

 

 

air outflow of the HRV/ERV should be "Y" connect-

 

Items for 2500HV & 4000HV

 

 

ed to the additional return duct then connected to

 

Flex or rigid duct

6” round

 

the inlet of the HEPA system.

 

(length as required)

 

 

• The additional return duct (if any) should be

 

Takeoffs

Two 6”

 

installed at least 6 ft. away from the outflow duct

 

Items for 6000V

 

 

on the main return.

 

Flex or rigid duct

10” round & 8” round

 

• Duct both the HRV/ERV and the additional return

 

(length as required)

 

 

into the intake of the HEPA system.

 

Takeoffs

One 10” & One 8”

 

Outflow (Marked as ‘Clean Air Out’ on unit):

 

Items for 6500, 8500 & 10000

 

 

 

 

 

Flex or rigid duct

12” round or 10” x 12”

 

• Outflow duct should be installed as close to the air

 

handler/furnace inlet as possible but not directly

 

(length as required)

 

 

into the return air elbow of the main return.

 

Takeoffs

Two 10”x12”

 

Ducting:

 

All Models

 

 

 

 

 

Aluminum tape or mastic as required

 

• If HEPA system is installed where inlet and outflow

 

collars face down, metal elbows must be connected

 

Misc. hanging materials - field provided

 

to both inlet and outflow collars.

 

NOTE: Be sure to review ‘Rules for Safe Installation

 

• Each connection must be sealed with aluminum

 

and Operation’ on page 1 of this document before

 

tape or mastic, including all take offs.

 

start-up of this unit.

 

 

• Installed duct runs should be as straight as possi-

10

Page 10
Image 10
Americair 8500 & 10000, 4000HV, 2500HV and Operation’ on page 1 of this document before, start-upof this unit, Preparation