American Aldes DH-100V specifications Specifications, Installation, Location, A L D E S D H

Models: DH-100V

1 10
Download 10 pages 45.11 Kb
Page 1
Image 1
DH-100V

DH-100V

HIGH EFFICIENCY DEHUMIDIFIER
INSTALLATION

OPERATION

MAINTENANCE

972DH 09-12

A L D E S D H - 1 0 0 V

Installation, Operation & Service Instructions
Table of Contents

1.

Specifications

1

2.

Installation

1

 

2.1 Location

1

 

2.1A In humid area, no ducting

1

 

2.1B In humid area, duct inlet and/or outlet

1

 

2.1C In remote area, duct inlet & outlet

2

 

2.1D In remote area, duct outlet only

2

 

2.1E In remote area, duct inlet only

2

2.2

Electrical Requirements

2

2.3

Condensate Removal

2

2.4

Ducting

2

 

2.4A Optional Ducting

2

 

2.4B Ducting for Dehumidification

2

 

2.4C Ducting for Fresh Air

3

3.

Operation

3

3.1

Humidity Control Adjustment

3

3.2

Fan Switch

3

4.

Maintenance

3

4.1

Air Filter

3

4.2

Blower Oiling

3

5.

Service

4

5.1

Warranty

4

5.2

Technical description

4

5.3

Troubleshooting

4

5.4

Refrigerant Charging

5

5.5

Blower Replacement

5

5.6

Compressor/Capacitor Replacement

5

 

5.6A Checking Compressor Motor Circuits

5

 

5.6B Replacing a Burned Out Compressor

5

 

5.6C Replacing a Compressor- Nonburn Out

6

5.7

Humidity Control

6

5.8

Defrost Thermostat

6

5.9

Condensate Pump

6

6.

Wiring Diagrams

7

7.

Service Parts List

8

8.

Warranty

9

9.

Service Notes

10

Serial No.________________________________Purchase Date____________________________Dealer's Name____________________________

Read the installation, operation and maintenance instructions carefully before installing and using this unit. Proper adherence to these instructions is essential to obtain maximum benefit from your DH-100V dehumidifier.

1 Specifications

Model: DH-100V Dehumidifier

Electrical: 110-120 VAC, 6.8 Amps, grounded

Capacity: 100 pints/day @ 80°F, 60% RH

Operating Temp. Range: 53°F min, 105°F max

Air Flow: 255 CFM without external ducting 170 CFM @ 0.15 in.wg. external static

Refrigerant Charge: 1 lbs., 14oz. R-22

Optional Duct connections: 8" round inlet & outlet

Size (w/o duct collars): 20" long x 17" wide x 36" high

Weight: 103 lbs.

2 Installation

2.1 Location

The DH-100V can be installed in a variety of locations to meet the owner's needs as listed below. In all cases, keep the following cautions in mind:

It is designed to be installed INDOORS ONLY.

If used near a pool or spa, be certain there is NO chance the unit could roll into the water or be splashed and that it is plugged into a GROUND

FAULT INTERRUPTER.

DO NOT use the DH-100V as a bench or table.

Avoid discharging the air directly at people, especially in pool areas.

2.1A In humid area, no ducting.

The simplest installation is to place the DH-100V in the humid area with no ducting. The air inlet on top & outlet on the side must be at least 1' from walls and other obstructions to air flow.

2.1B In humid area, duct inlet and/or outlet.

If the humid area is very large or has high ceilings, dehumidification can be improved by adding an inlet and/or outlet duct to circulate and destratify stagnant areas. For a large area, add inlet or outlet ducting to create flow across the area's greatest length.

For areas with ceilings higher than 12', use an inlet duct to draw warm, moist air from near the ceiling. See section 2.4 for attaching duct collars & ducting.

1

Page 1
Image 1
American Aldes DH-100V specifications Specifications, Installation, Location, 2.1A In humid area, no ducting, Serial No