IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left side panel behind top/access control door. In the case of 208 V AC
or 240 VAC, the supply voltage must match the electric service specifications of the
data label exactly.
WARNING: 208 V AC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.
IMPORTANT: 380, 400, and 416 Volt dryers are built 4-wire only. Customer must contact the
factory to special order 3-wire systems.
ADE-11 5ES ( 72 Kw Ele ctric Ove n ) Re ve rsing, 3ø MotorELECTR ICAL SE R V ICE SP EC IFICAT IO NS (P ER D RY E R )
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A.When fuses are used they must be dual element, time delay, current limiting, class RK1or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.
B.Circuit breakers are thermal-magnetic (industrial) type ONLY. For othe rs , c al cu l ate / ve ri fy c o rrec t bre ak e r si z e acc ord i ng to
appliance amp draw rating and type of breaker used.
C.Ci rcu i t b rea ke rs for 3 -p has e (3Ø) d rye rs mu st be 3-pole type.
OVEN SIZE
(Kw) SERVICE
VOLTAGE PHASE WIRE
SERVICE
APPROX.
AMP DRAW MINIMUM
WIRE SIZE
FUSING CIRCUIT
BREAKER
60 Hz 50 Hz Dual Element
Time Delay
72 208 3ø 3 214 -- * 300 300
72 240 3ø 3 188 190 * 250 250
72 380 3ø 4** -- 118 * 150 150
72 400 3ø 4** -- 112 * 150 150
72 416 3ø 4** -- 108 * 150 150
72 460 3ø 3 98 -- * 125 125
72 480 3ø 3 94 -- * 125 125
72 575 3ø 3 78 -- * 100 110
*AWG Stranded Wire Type...size wire as p er Nati o nal E l e ctrical Co de o r l ocal co d es .
(Motor lead wire is recommended.)
**3-wire available.