2.Electrical Service Specifications
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse valve, by applying either local and/or National Electrical Codes to listed appliance amp draw data.
B.Circuit breakers are
C.Circuit breakers for
SERVICE |
| WIRE | APPROX. | MINIMUM | FUSING | CIRCUIT | ||||
PHASE | Dual Element | |||||||||
AMP DRAW | BREAKER | |||||||||
VOLTAGE | SERVICE | WIRE SIZE | Time Delay | |||||||
|
|
| 60 Hz | 50 Hz |
| 60 Hz | 50 Hz | 60 Hz | 50 Hz | |
208 | 3ø | 3/4 | 11.8 | * | 20 | 20 | ||||
|
|
|
|
|
|
|
|
|
| |
240 | 3ø | 3 | 13.0 | 16.7 | * | 20 | 25 | 20 | 25 | |
| 3ø | 3/4 | 8.0 | * | 15 | 15 | ||||
|
|
|
|
|
|
|
|
|
| |
416 | 3ø | 3/4 | 8.4 | * | 15 | 15 | ||||
|
|
|
|
|
|
|
|
|
| |
460/480 | 3ø | 3/4 | 7.0 | * | 15 | 15 | ||||
|
|
|
|
|
|
|
|
|
| |
575 | 3ø | 3 | 5.8 | * | 15 | 15 | ||||
|
|
|
|
|
|
|
|
|
|
*AWG Stranded Type Wire ... size wire as per National Electrical Code or local codes. (Motor lead type wire is recommended).
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the left side panel/wall area behind the control door. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.
WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.