ADE-120 II (72 Kw Electric)

Reversing, 3ø

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.

C.

208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local or National Electrical Codes to listed appliance amp draw data.

Circuit breakers are thermal-magnetic (industrial) type ONLY . For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

OVEN SIZE

SERVICE

 

WIRE

APPROX.

PHASE

AMP DRAW

(Kw)

VOLTAGE

SERVICE

 

60 Hz

50 Hz

 

 

 

 

 

 

 

 

 

 

72

208

3

212

---

 

 

 

 

 

 

72

240

3

186

190

 

 

 

 

 

 

72

380-400

3

---

117

 

 

 

 

 

 

72

380-400

4

---

117

 

 

 

 

 

 

72

416

3

---

108

 

 

 

 

 

 

72

416

4

---

108

 

 

 

 

 

 

72

460/480

3

97

---

 

 

 

 

 

 

72

575/600

3

78

---

 

 

 

 

 

 

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the left side panel/wall area behind the control door. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.