American Dryer Corp ADG-530 HSI System Operation Flow Chart, Computer Calls For Heat

Models: ADG-530

1 18
Download 18 pages 34.76 Kb
Page 8
Image 8

f.The Hot Surface Ignitor will turn on and after approximately four (4) seconds the Hot Surface Ignitor will shut off. The Gas Valve will be energized and a burner flame should be evident for approximately severn (7) seconds and then shut off.

g.The HSI Module will attempt two (2) additional ignition trials after which the HSI Module will LOCKOUT and the “red” indicator light will flash 3 blinks, wait one (1) second, and then keep flashing 3 blinks continuously until the HSI Module is reset manually.

h.Functional check of the HSI (Hot Surface Ignition) Module is complete.

2.HSI SYSTEM OPERATION (Flow Chart)

Hot Surface Ignitor

Starts

To

Glow

HSI Module Enters

Internal Routine Check

L.E.D. Indicator

Stays On Approx. 4 Seconds

Computer

Calls

For Heat

If L.E.D. Indicator

If L.E.D. Continuously

Blinks Twice in Succession

Stays On Continuously

There Is a Fault In The

Replace HSI Module

Heat Sensing Circuit

Approx. 4 Seconds Later

Gas Valve Opens

Approx. 4 Seconds Later Hot Surface Ignitor Shuts Off

Ignition Evident?

(FLAME VERIF IED)

--------------------

YES NO

Open and Close Main Door

Restart Dryer

HSI Module LOCKOUT

-------------------------- ------

Module L.E.D. Will Continuously

Blink 3 Times In Succession

 

HSI Module Will Wait 15-17 Seconds

 

 

Flame Not

 

 

And Then Go Into Retry Mode

 

 

 

 

 

 

Established

 

 

 

 

 

 

 

HSI Module Will Attempt To Retry Twice

 

 

After Retrys

 

 

 

 

 

 

 

 

 

 

 

Normal Heating Cycle

Flame Out

FLAM E NOT VERIFIED

HSI Module Will Wait 15-17 Seconds And Then Go Into Retry Mode

HSI Module Will Attempt To Retry 3 Times

6

Page 8
Image 8