User Configuration Items
Note: Setting these items requires optional software or hardware.
Function | Factory Default | User Selectable Choices | Description |
Automatic | Every 14 days | Every 7 days (168 hours), On | Sets the interval at which the UPS will execute a |
| (336 hours) | Startup Only, No |
|
|
|
|
|
UPS ID | UPS_IDEN | Up to eight characters to define | Use this field to uniquely identify the UPS for network |
|
| the UPS. | management purposes. |
|
|
|
|
Date of Last Battery Replacement | Manufacture Date | Date of Battery Replacement | Reset this date on battery replacement. |
Minimum Capacity Before Return from | 0 percent | 15, 50, 90 percent | The UPS will charge its batteries to the specified percentage |
Shutdown |
|
| before return from a shutdown. |
|
|
|
|
Sensitivity | Normal | Reduced, Low | Set lower than normal sensitivity to avoid lowered battery |
|
|
| capacity and service life in situations where the load can |
|
|
| tolerate minor power disturbances. |
|
|
|
|
Duration of Low Battery Warning | 2 minutes | 5, 7, 10 minutes | Sets the time before shutdown at which the UPS issues a low |
|
|
| battery warning. Set higher than the default only if the OS |
|
|
| needs the time for graceful shutdown. |
|
|
|
|
Alarm Delay After Line Fail | 5 second delay | 30 second delay, At Low Battery | To avoid alarms for minor power glitches, set the alarm delay. |
|
| Condition, No Alarm |
|
|
|
|
|
Shutdown Delay | 20 seconds | 180, 300, 600 seconds | Sets the interval between when the UPS receives a shutdown |
|
|
| command and when shutdown occurs. |
|
|
|
|
Synchronized | 0 seconds | 60, 180, 300 seconds | To avoid branch circuit overload, the UPS will wait the |
|
|
| specified time after the return of utility power before |
|
|
|
|
High Transfer Point | 253 | 264, 271, 280 | To avoid unnecessary battery usage, set the High Transfer |
|
|
| Point higher if the utility voltage is chronically high and the |
|
|
| load is known to work well under this condition. |
|
|
|
|
Low Transfer Point | 196 | 188, 204, 208 | Set the Low Transfer Point lower if the utility voltage is |
|
|
| chronically low and the load can tolerate this condition. |
|
|
|
|
How to Determine On-Battery Run Time
Note:
UPS battery life differs based on usage and environment.
Tower and 5U Rack Mount 5000 VA Models
Typical
Load | 5000 VA Internal Battery |
100 VA | 7.17 |
150 VA | 5.95 |
200 VA | 5.04 |
300 VA | 3.88 |
400 VA | 2.96 |
500 VA | 2.37 |
600 VA | 1.92 |
800 VA | 1.40 |
1000 VA | 1.06 |
1200 VA | 0.83 |
1400 VA | 0.65 |
1600 VA | 0.54 |
2000 VA | 0.39 |
2200 VA | 0.33 |
2500 VA | 0.26 |
3000 VA | 0.19 |
3500 VA | 0.16 |
4000 VA | 0.13 |
4500 VA | 0.11 |
5000 VA | 0.09 |
11 |