Determine the Location of the UPS in the Rack (continued)
1.Determine where in the rack you’ll mount the UPS. The SU5000 requires a space of 5U. Some racks have tick marks to indicate
| the |
|
2. | Using the mounting template provided (part number | |
| identify and mark the correct mounting holes for the UPS | |
| mounting brackets. |
|
3. | Locate and mark the bottom hole in the designated | |
The bottom screw on the mounting rail will attach to the bottom | ||
hole in the |
| |
|
| |
4. | Repeat steps 3 and 4 for the remaining three rack posts. | |
5. | Prepare the rack holes, if necessary. Racks with threaded holes | |
| require no preparation. |
|
| If your rack has round holes, insert clip nuts | (provided) into |
| the holes in step 2. |
|
| If your rack has square holes, insert either clip | or cage |
| nuts into the holes marked in step 2 (cage nut shown). | |
Install the Mounting Rails in the Rack | 2 |
|
1 |
|
Remove the two screws that hold the rails together so that the rails can slide outward . Do not detach the rails.
Front
Align the bottom hole on the mounting rail with the bottom hole in the
3 | 4 |
Expand the rails so that it spans from the front rack post to the back rack post. Replace the two screws (removed in step 1) that hold the rail sections together.
Back
Attach the rail to the back rack post using the same hardware
Caution:
3 |