American Power Conversion 60-80kW 208/480V manual Acoustic alarm sounds for 30 secs

Models: 60-80kW 208/480V

1 34
Download 34 pages 63.25 Kb
Page 13
Image 13

Stop/Start UPS and Operating the External Service Bypass

Action

Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass operation

1.

Press

on the keyboard

Display shows

 

2.

Press

or

on the keyboard until

Bypass operation

 

 

 

 

: NO

3.

Press

on the keyboard

Bypass operation

 

 

 

 

: YES

4.

Press

on the keyboard

 

All systems switch to bypass operation

Do not switch off any of the UPS systems until steps 5-8 have been completed

5.Check light indication on the bypass panel

6.Set the external bypass switch (Q003) to position 1

7.Set the output switch (Q004) to position 0

8.Set all output switches (Q002) to position 0

9.Open the front door of any one system and press the red OFF button

The acoustic alarm sounds for 30 secs* Repeat for (all) other system(s)

10.Set all input switches (Q001) to position 0

The red alarm LED below the display lights up and

the acoustic alarm sounds for 30 secs*

*Reset the acoustic alarm by pressing thekey.

Bypass operation

Lamp indication on Bypass Panel

Green light (H003) above the bypass switch handle (Q003) lights up

Green light (H004) above the output switch handle (Q004) and green lights (H002) above the output switch handles (Q002) light up

H003 switches off

H002 and H004 still on

H002 and H004 still on

Display shows

**System OFF**

 

990-4035

 

 

User Guide APC Silcon 60-80kW 208V/480V UPS

13

Page 13
Image 13
American Power Conversion 60-80kW 208/480V manual Acoustic alarm sounds for 30 secs