Alarms and Events

 

 

 

 

 

 

 

 

 

 

 

40.

RAM1 memory write error

UPS fault

Call for assistance

 

 

 

 

 

 

41.

Memory write error

UPS fault

Call for assistance

 

 

 

 

 

42. Communication to VQ bypass

UPS fault

Call for assistance

 

 

lost

 

 

 

 

 

 

 

43. Communication to VQ output

UPS fault

Call for assistance

 

 

lost

 

 

 

 

 

 

 

 

44.

Communication to DMU lost

UPS fault

Call for assistance

 

 

 

 

 

 

45.

Communication to controller

UPS fault.

Call for assistance

 

 

lost

Display will show invalid UPS

 

 

 

 

data

 

 

 

 

 

 

 

46.

Communication to parallel IF

UPS fault

Call for assistance

 

 

lost

 

 

 

 

 

 

 

 

47.

External shutdown accepted

Remote signal for switching off

 

 

 

UPS accepted.

 

 

 

 

UPS switches off automatically

 

 

 

 

 

 

 

48.

Communication to VQ mains

UPS fault

Call for assistance

 

 

lost

 

 

 

 

 

 

 

 

49.

Bypass syncronization error

The UPS cannot synchronize with

Check if phase rotation of bypass

 

 

 

bypass mains

voltage is correct – if OK, call for

 

 

 

 

assistance

 

 

 

 

 

 

50.

Battery charge error

Transferred to battery operation

Check RFI input fuse and

 

 

 

because of battery charge error

feedback relay

 

 

 

 

 

5.4Rectifying Alarm Messages

Following actions may rectify alarm:

Check local utility supply. Fuses may be blown or supply switched off accidentally

Check if UPS cooling air intake is blocked

Check if load exceeds maximum output capacity

If, with utility power switched on, there is no UPS output voltage - and an attempt to restart the UPS is in vain - use the external service bypass switch to bypass UPS

1.“Battery weak” message appears: Reset “battery weak” signal according to section 4.0 Parameter Settings and initiate battery capacity test according to Section 6.3. Battery Capacity Test. Make a record of obtained back-up time and use battery monitor to reset alarm. Leave the UPS to recharge battery for at least 16 hours. Start up second battery test without changing the load. If the test result shows improved back-up time, continue the test series until no or just insignificant improvements are obtainable. If battery is still weak - call for assistance.

2.“Battery Defective” message appears: Call for assistance. See section 8.0 “How to contact APC”.

990-4035

User Guide APC Silcon 60-80kW 208V/480V UPS

27

Page 27
Image 27
American Power Conversion 60-80kW 208/480V manual Rectifying Alarm Messages