Operation

3.2Display of Measured Values

To read measurements, press one or two keys simultaneously as shown below. (Illustrated values are examples only).

NOTICE!

Please note mains = utility

Action

Display shows

98.01.16 System off 10.22,13

Mains 1 voltage 480 480 480Vac

Mains 1 current

16 16 16Aac

Battery voltage

System off 438 437Vdc

Battery current

+ 2Adc

Output voltage 480 480 480Vac

Output current

15 15 15Aac

Output frequency

60Hz

Battery temperature

25°C

Output peak current

22 22 22A

Normal operation load power xx%

Batt. load : 0

Batt. tank: 100

Description

Year, month, day

Hour, minute, second

Utility 1 voltage is 3 x 480V

Utility 1 current is 3 x 16A

Battery voltage is 438Vdc on battery 1 437Vdc on battery 2

Charging current is (+) 2 Adc (Discharging current ())

Output voltage is 3 x 480V

Output current is 3 x 15A

Output frequency is 60Hz

Battery temperature is 25°C (77°F)

Output peak current is 3 x 22A

Returns to normal status indication. If not pressed, automatic switch back will be performed after 20 seconds.

Battery load in percent.

Left battery capacity in percent.

 