American Power Conversion 60-80kW 208/480V manual Bypassing the Single System UPS

Models: 60-80kW 208/480V

1 34
Download 34 pages 63.25 Kb
Page 9
Image 9

Stop/Start UPS and Operating the External Service Bypass

2.5Operating the External Service Bypass Switch (single systems)

2.5.1 Bypassing the Single System UPS

 

 

 

Utility

Load

 

 

 

 

 

 

 

Service Bypass

 

 

 

 

Switch

 

 

 

 

APC Silcon

 

 

 

 

UPS

 

Action

 

 

Display shows

1.

Press

on the keyboard

 

2.

Press

or

on the keyboard until

Bypass operation

: NO

 

 

 

 

3.

Press

on the keyboard

Bypass operation

: YES

 

 

 

 

4.

Press

on the keyboard

 

 

 

 

 

Lamp indication on

 

 

 

 

Bypass Panel

5.Check light indication on the bypass panel

6.Set the external bypass switch (Q003) to position 1

7.Set the output switch (Q002) to position 0

8.Open the front door and press the red OFF button

The acoustic alarm sounds for 30 seconds*

9.Set the input switch (Q001) to position 0

The red alarm LED below the display lights up and the acoustic alarm sounds for 30 seconds*

*Use the key to reset the acoustic alarm

Green light (H003) above the bypass switch handle (Q003) lights up

Green light (H002) above the output switch handle (Q002) lights up

Only the light (H002) above the output switch handle (Q002) is now on

Display shows

**System OFF**

 

990-4035

 

 

User Guide APC Silcon 60-80kW 208V/480V UPS

9

Page 9
Image 9
American Power Conversion 60-80kW 208/480V manual Operating the External Service Bypass Switch single systems