Specifications

Environmental Specifications

Temperature

32° to 104° F (0° to 40° C)

This unit is intended for indoor use only.

Operating

Select a location sturdy enough to handle

Storage

5° to 113° F (-15°to 45° C) charge the UPS battery every

the weight.

 

six months

Do not operate the UPS where there is

 

86° to 158° F (30° to 70° C) charge the UPS battery every

 

three months

excessive dust or the temperature or

 

 

humidity are outside the specified limits.

Maximum

 

 

This unit has front to rear airflow. Allow

Elevation

 

 

adequate space for proper ventilation.

Operating

10,000 ft (3,000 m)

Environmental factors impact battery life.

Storage

50,000 ft (15,240 m)

 

 

High temperatures, poor utility power, and

Humidity

0 to 95% relative humidity, non-condensing

frequent, short duration discharges will

 

 

shorten battery life.

Physical Specifications

 

 

 

 

 

 

 

 

 

 

Weight (unpacked)

 

 

 

 

 

 

 

 

 

 

 

XLBP

 

 

 

 

 

with eight battery

400 lbs (181 kg)

 

 

 

 

modules

 

 

 

 

 

 

 

 

 

 

 

Each battery

38 lbs (17 kg)

 

 

 

 

module

 

 

 

 

 

 

 

 

 

 

Dimensions

 

 

 

 

 

482 mm

 

 

 

19 in

 

 

 

465 mm

 

 

 

18.3 in

693 mm

 

 

432 mm

27.3 in

 

 

 

 

 

17 in

 

263 mm 10.4 in

102 mm

4 in

 

 

 

 

739 mm

 

 

 

29.1 in

4

SURT192RMXLBP2/SURT192XLBP2 6U User Manual

Page 4
Image 4
American Power Conversion 990-2485 user manual Environmental Specifications, Physical Specifications