American Power Conversion AFX Series manual Performance Data, Air system, Coolant requirements

Models: AFX Series

1 80
Download 80 pages 46.06 Kb
Page 26
Image 26

Performance Data

Air system

AIR/WATER/

MODEL

6T

8T

10T

12T

14T

18T

20T

26T

28T

GLYCOL/RC

 

 

 

 

 

 

 

 

 

 

Air Volume (CFM)

 

4,200

4,400

7,000

7,200

8,400

8,800

12,600

13,200

14,200

(L/s)

 

(1,982)

(2,077)

(3,304)

(3,398)

(3,965)

(4,154)

(5,947)

(6,230)

(6,702)

Fan Motor HP (qty)

 

3 (1)

3 (1)

3 (2)

3 (2)

3 (2)

3 (2)

3 (3)

3 (3)

3 (3)

(kW)

 

(2.2) (1)

(2.2) (1)

(2.2) (2)

(2.2) (2)

(2.2) (2)

(2.2 (2)

(2.2) (3)

(2.2) (3)

(2.2) (3)

External Static Pressure (inches)

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

(Pa)

 

(125)

(125)

(125)

(125)

(125)

(125)

(125)

(125)

(125)

Number of Fans

 

1

1

2

2

2

2

3

3

3

 

 

 

 

 

 

 

 

 

 

 

Coolant requirements

WATER

MODEL

6T

8T

10T

12T

14T

18T

20T

26T

28T

65° F Water In (GPM)

6.2

8.9

10.1

11.7

11.4

17.9

20.2

23.1

23.4

(18.3° C) (L/s)

 

(0.4)

(0.6)

(0.6)

(0.7)

(1.7)

(1.1)

(1.3)

(1.5)

(1.5)

Pressure Drop (psig)

 

3.2

4.9

4.8

3.8

2.9

4.8

4.9

4.6

4.7

(kPa)

 

(22.1)

(33.8)

(33.1)

(26.2)

(20.0)

(33.1)

(33.8)

(31.7)

(32.9)

THR (MBH)

 

114,435

160,827

195,092

216,444

228,736

323,814

374,456

444,410

456,066

(kW)

 

(33.5)

(47.1)

(57.1)

(63.4)

(67.0)

(94.8)

(109.6)

(130.1)

(133.5)

 

 

 

 

 

 

 

 

 

 

75° F Water In (GPM)

8.3

11.8

13.4

15.6

15.2

23.9

26.9

30.8

31.2

(23.9 °C)(L/s)

 

(0.5)

(0.7)

(0.8)

(1.0)

(1.0)

(1.5)

(1.7)

(1.9)

(2.0)

Pressure Drop (psig)

 

5.7

8.7

8.6

6.7

5.2

8.6

8.7

8.1

8.3

(kPa)

 

(39.3)

(60.0)

(59.3)

(96.2)

(35.9)

(59.3)

(60.0)

(55.9)

(57.2)

THR (MBH)

 

114,435

160,827

195,092

216,444

228,736

323,814

374,456

444,410

456,066

(kW)

 

(33.5)

(47.1)

(57.1)

(63.4)

(67.0)

(94.8)

(109.6)

(130.1)

(133.5)

 

 

 

 

 

 

 

 

 

 

85° F Water In (GPM)

18.6

25.7

28.4

33.8

30.7

52.1

58.1

65.8

69.3

(29.4 °C) (L/s)

 

(1.2)

(1.6)

(1.8)

(2.1)

(1.9)

(3.3)

(3.7)

(4.2)

(4.4)

Pressure Drop (psig)

 

27.3

39.9

37.6

30.1

20.8

39.3

39.4

36.1

39.9

(kPa)

 

(188.3)

(275.1)

(259.3)

(207.6)

(143.9)

(271.0)

(271.7)

(249.0)

(275.2)

THR (MBH)

 

114,435

160,827

195,092

216,444

228,736

323,814

374,456

444,410

456,066

(kW)

 

(33.5)

(47.1)

(57.1)

(63.4)

(67.0)

(94.8)

(109.6)

(130.1)

(133.5)

 

 

 

 

 

 

 

 

 

 

 

GLYCOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105° F Glycol In (GPM)

17.5

25.2

31.0

31.7

34.9

50.8

61.4

66.9

67.8

(40.6 °C) (L/s)

 

(1.1)

(1.6)

(2.0)

(2.0)

(2.2)

(3.2)

(3.9)

(4.2)

(4.3)

Pressure Drop (psig)

 

12.0

21.5

26.2

26.1

9.3

11.0

11.8

10.2

10.5

(kPa)

 

(82.8)

(148.3)

(180.7)

(180.0)

(64.1)

(75.9)

(81.4)

(70.3)

(72.4)

THR (MBH)

 

110,543

156,191

188,188

208,802

220,638

313,448

361,520

432,200

442,906

(kW)

 

(32.4)

(45.7)

(55.1)

(61.1)

(64.6)

(91.8)

(105.9)

(126.6)

(129.7)

 

 

 

 

 

 

 

 

 

 

 

Pump system

GLYCOL

MODEL

6T

8T

10T

12T

14T

18T

20T

26T

28T

Horsepower

 

3/4

3/4

1

1

1

1-1/2

2

3

3

Total Head (feet) (@ design GPM)

62

59

69

68

65

65

80

92

92

(m)

 

(18.9)

(18.0)

(21.0)

(20.7)

(19.8)

(19.8)

(24.4)

(28.0)

(28.0)

Available Ext. Head (feet)

28

33

27

26

37

37

51

62

61

(m)

 

(8.5)

(10.1)

(8.2)

(7.9)

(11.3)

(11.3)

(15.5)

(18.9)

(18.6)

 

 

 

 

 

 

 

 

 

 

 

APC NetworkAIR AFX Series: Performance Data

21

Page 26
Image 26
American Power Conversion AFX Series manual Performance Data, Air system, Coolant requirements, Pump system