APC NetworkAIR AFX Series: Performance Specifications 19

Net cooling capacityglycol
MODEL
CAPACITY IN BTU/H 6T 8T 10T 12T 14T 18T 20T 26T 28T
80° F DB, 67° F WB Total (BTUH) 77,700 110,700 130,200 145,800 155,300 225,100 270,000 296,400 328,700
(26.7°C DB, 19.4°C WB) (kW) (22.8) (32.4) (38.1) (42.7) (45.5) (65.9) (79.1) (86.8) (96.2)
50% RH Sensible (BTUH) 72,300 88,800 123,400 133,600 150,100 184,000 241,000 257,900 282,900
(kW) (21.2) (26.0) (36.1) (39.1) (44.0) (53.9) (70.6) (75.5) (82.8)
75° F DB, 62.5° F WB Total (BTUH) 7 1,900 102,000 121,600 133,900 145,800 206,800 256,400 274,400 302,100
(23.9°C DB, 16.9°C WB) (kW) (21.1) (29.9) (35.6) (39.2) (42.7) (60.6) (75.1) (80.3) (88.5)
50% RH Sensible (BTUH) 70,300 87,400 121,600 130,600 145,800 179,900 210,600 251,800 277,500
(kW) (20.6) (25.6) (35.6) (38.2) (42.7) (52.7) (61.7) (73.7) (81.3)
75° F DB, 61° F WB Total (BTUH) 69,597 100,600 121,600 129,294 145,700 201,700 254,400 278,700 305,200
(23.9°C DB, 16.1°C WB) (kW) (20.4) (29.5) (35.6) (37.9) (42.7) (59.1) (74.5) (81.6) (89.4)
45% RH Sensible (BTUH) 69,597 94,400 121,600 129,294 145,700 193,600 216,500 278,700 305,200
(kW) (20.4) (27.6) (35.6) (37.9) (42.7) (56.7) (63.4) (81.6) (89.4)
72° F DB, 60° F WB Total (BTUH) 69,000 97,300 116,100 127,500 139,300 197,200 237,700 266,400 285,400
(22.2°C DB, 15.5°C WB) (kW) (20.2) (28.5) (34.0) (37.3) (40.8) (57.7) (69.6) (78.0) (83.6)
50% RH Sensible (BTUH) 69,000 85,300 116,100 125,500 139,300 175,500 230,600 251,800 265,100
(kW) (20.2) (25.0) (34.0) (36.7) (40.8) (51.4) (67.5) (73.7) (77.6)
72° F DB, 58.6° F WB Total (BTUH) 6 8,310 96,200 116,100 124,245 139,300 193,000 241,600 268,600 292,500
(22.2°C DB, 14.8°C WB) (kW) (20.0) (28.2) (34.0) (36.4) (40.8) (56.5) (70.7) (78.6) (85.6)
45% RH Sensible (BTUH) 68,310 91,200 116,100 124,245 139,300 188,500 241,600 268,600 292,500
(kW) (20.0) (26.7) (34.0) (36.4) (40.8) (55.2) (70.7) (78.6) (85.6)
70° F DB, 58.5° F WB Total (BTUH) 6 6,900 94,400 112,500 125,200 135,100 191,100 230,600 259,300 278,600
(22.2°C DB, 14.8°C WB) (kW) (19.6) (27.6) (32.9) (36.7) (39.6) (56.0) (67.5) (75.9) (81.6)
50% RH Sensible (BTUH) 66,900 83,500 112,500 125,200 135,100 171,900 225,300 247,100 265,100
(kW) (19.6) (24.4) (32.9) (36.7) (39.6) (50.3) (66.0) (72.4) (77.6)
70° F DB, 57.2° F WB Total (BTUH) 6 6,900 93,300 112,500 125,100 135,000 187,300 234,600 261,900 284,100
(22.2°C DB, 14.8°C WB) (kW) (19.6) (27.3) (32.9) (36.6) (39.5) (54.8) (68.7) (76.7) (83.2)
45% RH Sensible (BTUH) 66,900 89,400 112,500 125,100 135,000 183,800 234,600 261,900 284,100
(kW) (19.6) (26.2) (32.9) (36.6) (39.5) (53.8) (68.7) (76.7) (83.2)
*Performance Specifications @ 95° F Ambient (AIR/GLYCOL/RC) or @ 105° F Condensing (WATER)