APC NetworkAIR AFX Series: Electrical Data 25

Electrical Data

Electric Reheat614 ton

HUMIDIFIER Electric Steam or No ne
VOLTAG E 208 230 460 575 208 230 460 575
6T FLA Air 42.4 42.4 21.1 17.5 41.6 42.4 21.1 17.5
Water 40.1 40.1 20.0 16.5 39.3 40.1 20.0 16.5
Glycol 43.9 4 3.9 21. 9 18.1 43.1 43.9 21.9 18.1
Remote Condensing 40.8 40.0 20.0 16.7 24.4 25.2 12.6 10.7
WSA Air 55.2 55.4 27.3 22.8 54.2 55.4 27.3 22.8
Water 55.2 55.4 27.3 22.8 54.2 55.4 27.3 22.8
Glycol 55.2 5 5.4 27. 3 22.8 54.2 55.4 27.3 22.8
Remote Condensing 51.0 50.0 25.0 20.9 30.5 31.5 15.8 13.4
MOP Air 70.0 70.0 35.0 30.0 70.0 70.0 35.0 25.0
Water 70.0 70.0 35.0 30.0 70.0 70.0 35.0 25.0
Glycol 70.0 7 0.0 35. 0 30.0 70.0 70.0 35.0 25.0
Remote Condensing 50.0 50.0 25.0 25.0 35.0 35.0 15.0 15.0
8T FLA Air 51.1 51.1 25.5 21.0 50.3 51.1 25.5 21.0
Water 47.9 47.9 23.9 19.7 47.1 47.9 23.9 19.7
Glycol 53.2 5 3.2 27. 0 21.8 52.4 53.2 27.0 21.8
Remote Condensing 40.8 40.0 20.0 16.7 24.4 25.2 12.6 10.7
WSA Air 71.3 71.5 36.4 29.5 70.3 71.5 36.4 29.5
Water 71.3 71.5 36.4 29.5 70.3 71.5 36.4 29.5
Glycol 71.3 7 1.5 36. 4 29.5 70.3 71.5 36.4 29.5
Remote Condensing 51.0 50.0 25.0 20.9 30.5 31.5 15.8 13.4
MOP Air 100.0 100.0 50.0 45.0 100.0 100.0 50.0 40.0
Water 100.0 100.0 50.0 45.0 100.0 100. 0 50.0 40.0
Glycol 100.0 100.0 50.0 45.0 100.0 100.0 50.0 40.0
Remote Condensing 50.0 50.0 25.0 20.0 30.0 35.0 15.0 15.0
10T FLA Air 64.5 64.5 31.9 26.7 62.0 63.6 31.5 26.3
Water 64.5 64.5 31.9 26.7 59.7 61.3 30.3 25.4
Glycol 64.5 6 5.1 32. 2 26.9 63.5 65.1 32.2 26.9
Remote Condensing 65.2 65.2 32.6 27.4 48.8 50.4 25.2 21.4
WSA Air 81.5 83.1 42.0 35.0 80.7 83.1 42.0 35.0
Water 81.5 83.1 42.0 35.0 80.7 83.1 42.0 35.0
Glycol 81.5 8 3.1 42. 0 35.0 80.7 83.1 42.0 35.0
Remote Condensing 81.5 81.5 40.8 34.3 61.0 63.0 31.5 26.8
MOP Air 90.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0
Water 90.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0
Glycol 90.0 9 0.0 45. 0 35.0 90.0 90.0 45.0 35.0
Remote Condensing 70.0 70.0 35.0 30.0 50.0 60.0 30.0 25.0
12T FLA Air 66.9 66.5 32.3 26.7 64.9 66.5 32.3 26.6
Water 64.5 64.5 31.9 26.7 62.8 64.4 31.1 25.7
Glycol 69.7 6 7.9 33. 1 27.2 66.3 67.9 33.1 27.2
Remote Condensing 65.2 65.2 32.6 27.4 48.8 50.4 25.2 21.4
WSA Air 84.7 84.9 42.0 35.4 82.5 84.9 42.0 35.4
Water 84.7 84.9 42.0 35.4 82.5 84.9 42.0 35.4
Glycol 84.7 8 4.9 42. 0 35.4 82.5 84.9 42.0 35.4
Remote Condensing 81.5 81.5 40.8 34.3 61.0 63.0 31.5 26.8
MOP Air 100.0 90.0 45.0 35. 0 90.0 90.0 45.0 35.0
Water 100.0 90.0 45. 0 35.0 90.0 90.0 45.0 35.0
Glycol 100.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0
Remote Condensing 70.0 70.0 35.0 30.0 50.0 60.0 30.0 25.0
14T FLA Air 68.4 67.4 33.5 28.0 65.8 67.4 33.5 28.0
Water 64.8 65.1 32.4 27.0 63.5 65.1 32.4 27.0
Glycol 71.4 6 8.9 34. 3 28.6 67.3 68.9 34.3 28.6
Remote Condensing 65.2 65.2 32.6 27.4 48.8 50.4 25.2 21.4
WSA Air 84.7 84.9 42.0 35.4 82.5 84.9 42.0 35.4
Water 84.7 84.9 42.0 35.4 82.5 84.9 42.0 35.4
Glycol 84.7 8 4.9 42. 0 35.4 82.5 84.9 42.0 35.4
Remote Condensing 81.5 81.5 40.8 34.3 61.0 63.0 31.5 26.8
MOP Air 100.0 90.0 45.0 35. 0 90.0 90.0 45.0 35.0
Water 100.0 90.0 45. 0 35.0 90.0 90.0 45.0 35.0
Glycol 100.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0
Remote Condensing 70.0 70.0 35.0 45.0 50.0 60.0 30.0 25.0
FLA= Full Load Amperes MOP=Maximum Overcurrent Protection WSA=Wire Size Ampere
*Values are calculated based on 3 phase power