Revision A | MX28B-PDF Product Manual |
Knock-outs
Figure 3-3: Installation of Circuit Breakers
3.5 LOAD CONNECTIONS
Connection for –48VDC loads are made from standard size #10-32 two-hole lugs on 5/8” centers located directly next to the corresponding circuit breaker. The load returns connect to the –48VDC load return bus located behind each row of circuit breakers. The load return bus provides threaded holes for terminating 2-hole lugs. The return bus has provisions for 25 #10-32 lugs on 5/8” centers and 10 ¼”-20 lugs on 1” centers (all pairs can not be used simultaneously). Each DC load run should be bundled with its return for as much of the run length as possible. (Figure 3-4)
Load supply
Load return
Figure 3-4 load connections