MX28B 27
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETER DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
High Voltage Alarm {1}
[BATT/SET-ALM] An alarm that is generated if the magnitude of the
battery voltage rises above the high voltage threshold. Batt HV Alm m+
Minor
Low Voltage Alarm {1}
[BATT/SET-ALM] An alarm that is generated if the magnitude of the
battery voltage drops below the low voltage threshold. Batt LV Alm m+
Minor
High Temperature Alarm {1}
[BATT/SET-ALM] An alarm that is generated if the battery temperature
exceeds the high temperature threshold. Batt HT Alm m+
Minor
Low Temperature Alarm {1}
[BATT/SET-ALM] An alarm that is generated if the battery temperature
drops below the low temperature threshold. Batt LT Alm m+
Minor
RECTIFIER SETUP
Fail Safe Voltage {1}
[MODULES/RECT/PARAM] Rectifier default output voltage if communication with
the control unit fails. Rect Fail Safem+
-54.00 V
Communications Timeout {1}
[MODULES/RECT/PARAM] The maximum rectifier communications response time
allowed before a communications failure is declared. Rect Fail Commm+
1 min
Rectifier Information NOTE: This information can be viewed for each
rectifier installed by using the horizontal arrow
keys.
Rectifier Description
[MODULES/RECT/INFO] Displays the model number of the installed rectifier. Rect 1 Desc #
MRF28H54
Rectifier Current
[MODULES/RECT/INFO] A display of the dc output current for the individual
rectifier. Rect 1 Curr #
24.9 A
Current Limit Alarm
[MODULES/RECT/INFO] The status will be “ON” if the rectifier has been forced
into its current limited mode. Rect 1 CL #
OFF
Standby Alarm
[MODULES/RECT/INFO] The status will be “ON” if the control unit is holding the
rectifier in the standby mode. Rect 1 Stdby #
OFF
Fan Fail Alarm
[MODULES/RECT/INFO] The status will be “ON” if the rectifier fan has failed. Rect 1 FF #
OFF
Rectifier Fault Alarm (RFA)
[MODULES/RECT/INFO] The status will be on if the rectifier output has failed. Rect 1 RFA #
OFF
Rectifier Alarms
Current Limit Alarm {1}
[MODULES/RECT/SET-ALM] This alarm indicates that a rectifier has been forced into
the current limited mode. Rect CL Alm m+
n of N
Standby Alarm {1}
[MODULES/RECT/SET-ALM] This alarm indicates that the control unit is holding a
rectifier in the standby mode. Rect Stdby Almm+
n of N
Fan Fail Alarm {1}
[MODULES/RECT/SET-ALM] This alarm indicates that a rectifier fan has failed. Rect FF Alm m+
n of N