30 MX28B
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETER DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Output Relay Alarms
Output Relay 1 {1}
[SYSTEM/OUT-RLY/RLY-MAP] Output Relay 1 alarm can be “mapped” to activate
other output relays (“Ignore” activates no additional
relays).
Out-Rly 1 Alm m+
Ignore
Output Relay 6 {1}
[SYSTEM/OUT-RLY/RLY-MAP] Output Relay 6 alarm can be “mapped” to activate
other output relays (“Ignore” activates no additional
relays).
Out-Rly 6 Alm m+
Ignore
LVD SETUP
LVD Trip {1}
[MODULES/LVD/PARAM] LVD trip (disconnect) threshold voltage. LVD Trip m+
-42.00 V
LVD Restore {1}
[MODULES/LVD/PARAM] LVD restore (reconnect) threshold voltage. LVD Reset m+
-48.00 V
LVD Option {1}
[MODULES/LVD/SET-ALM] Set to “Enable” if the unit has an LVD. LVD Option m+
Enable
LVD Alarm
LVD Alarm {1}
[MODULES/LVD/SET-ALM] Sets the priority or “mapping” of an LVD Alarm. LVD Open Alm m+
Minor