INTRODUCTION
Thank you for choosing the APC SurgeArrest PMH3XLM Series Surge Protection Device (SPD).
This User Manual provides important information for the owner of APCs
Please read and understand all information contained in this manual prior to use. This manual is to be used as a guide for using the device.
The APC modular Surge Protection Device (SPD) is a high quality, high energy surge attenuation system that has been designed to protect sensitive equipment from damaging transient voltage surges in 380/220 volt power system applications. The PMH3XLM unit is a parallel SPD designed for service entrance and downstream panelboard applications. Proper use is imperative to maximize the surge suppressor’s effectiveness and performance.
The PMH3XLM provides surge protection per phase and is available with a 120kA per phase rating. All APC products are extensively tested according to industry standards as set by IEC 60950, and is qualified for all circuit capacities. Note: When planning the placement of this device, consideration should be given to the connection method to be used. In some applications, this device may require several feet of wire. Increased wire lead length adversely affects clamping voltages.
WARNINGS, CAUTIONS and NOTES
•Warnings statements in this manual provide information, which if not complied with, may result in personnel injury or death.
•Cautions statements in this manual provide information, which if not complied with, may result in damage to equipment.
•Notes presented in this manual contain information deemed essential to highlight.
INSTALLATION CONSIDERATIONS
For system deployment planning purposes, during installation into an electrical system, the SPD must NOT be energized until the electrical system is completely installed, inspected, and tested. All conductors must be connected and functional, including the neutral (blue wire). The voltage rating of the device and system must always be verified before energizing the SPD.
Failure to follow these guidelines can lead to abnormally high voltage being applied to the SPD. This may cause the SPD to prematurely fail or significantly shorten the effective life. The warranty does not cover an incorrectly installed device.
TESTING
Also for system deployment planning purposes, any factory or
Caution: The SPD and its associated suppression components must be disconneted during elevated voltage testing. Failure to comply may result in damage to the suppression components and/or other electronic components.
UNPACKING and PRELIMINARY INSPECTION
•Inspect the entire shipping container for damage or signs of mishandling before unpacking the unit.
•Remove the cardboard packing and further inspect the unit for any obvious shipping damages.
•If damage found is a result of shipping or handling, immediately file a claim with the shipping company and forward a copy to APC.
Page 1