**On
installed per national and local electrical codes.
Failure to comply may result in damage to the equipment.**
ELECTRICAL CONNECTIONS
Overcurrent Protection
The Surge Protection Device (SPD) draws very little current under normal conditions and will only conduct for a brief duration upon encountering a transient surge voltage. APC SPDs contain internal fusing to protect against abnormal voltage conditions. Note: Fuses are not replaceable.
Voltage Rating
Prior to having the SPD installed, verify that the unit has the correct voltage rating by checking the nameplate voltage or model number. The service type should match the intended power source. See Table 1 for the voltage rating and service type of the SPD.
Table 1: Voltage Rating and Service Type
Model Number
PMH3XLM
Terminals
Voltage Rating and Service Type
220/380 Volts, 3- Phase, WYE
Terminals have been provided inside the APC
! | WARNING | VERIFY THAT ALL POWER |
| ||
| CIRCUITS ARE | |
|
| |
|
| BEFORE MAKING CONNECTIONS |
|
|
|
All electrical connections should be performed by a qualified/licensed electrician. All wiring
must comply with national and applicable local codes.
Parallel Connection
When making a parallel type of connection (Figure 2), the length of the wiring to the Surge Protection Device (SPD) must be kept as short as possible to substantially enhance the performance. Long wire runs are to be avoided for the unit to perform as intended.
To reduce the impedance the wire displays to surge currents, the phase, neutral, and ground conductors are to be routed within the same conduit and should be tightly bundled or twisted together to optimize performance of the unit. Sharp bends in the conductors are to be avoided.
Wire Size
With a parallel connection, the size of the wiring to the SPD is independent of the ampere rating of the circuit to be protected. The recommended wire size is based on the unit’s transient surge current capabilities. #8 AWG is the recommended wire size for phase, neutral, and ground.
**Surge Protection Devices are designed for use on the load side
of the service entrance disconnect only**
Page 4