15
NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.
FUNCTION FACTORY
DEFAULT
USER SELECTABLE
CHOICES DESCRIPTION
High Transfer
Point
230V models:
253VAC
120V models:
132VAC
100V models:
110VAC
230V models:
264, 271,
280VAC
120V models:
129, 135,
138VAC
100V models:
108, 112,
114VAC
To avoid unnecessary battery usage, set
the high transfer point higher if the util-
ity voltage is chronically high and the
connected equipment is known to work
under this condition.
Low Transfer
Point
230V models:
196VAC
120V models:
103VAC
100V models:
90VAC
230V models:
188, 204,
208VAC
120V models:
97, 100, 106VAC
100V models:
81, 85, 92VAC
Set the low transfer point lower if the
utility voltage is chronically low and the
connected equipment can tolerate this
condition.
Output Voltage 230V models:
230VAC
230V models:
220, 225,
240VAC
230V models only; allow the user to se-