4: USER CONFIGURABLE ITEMS
NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.
FUNCTION FACTORY
DEFAULT
USER SELECTABLE
CHOICES DESCRIPTION
Automatic Self-
Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
On Startup Only,
No Self-Test
This function sets the interval at which
the UPS will execute a self-test. Refer to
your software manual for details.
UPS ID UPS_IDEN Up to eight char-
acters to define
the UPS
Use this field to uniquely identify the
UPS for network management purposes.
Date of Last
Battery Re-
placement
Manufacture
Date
Date of Battery
Replacement
Reset this date when you replace the
battery module.
Minimum Ca-
pacity Before
Return from
Shutdown
0 percent 15, 50, 90 percent The UPS will charge its batteries to the
specified percentage before return from
a shutdown.
Sensitivity High Medium, Low Set lower than high sensitivity to avoid
lowered battery capacity and service life
in situations where the connected equip-
ment can tolerate minor power distur-
bances.
Duration of Low
Battery Warning
2 minutes 5, 7, 10 minutes This function sets the time before shut-
down. The UPS issues a low battery
warning. Set it higher than the default if
the operating system needs more time
for shutdown.
Alarm Delay
After Line Fail
5 second delay 30 second delay at
low battery condi-
tion only. No
alarm for line fail.
To avoid alarms for minor power
glitches, set the alarm delay.
Shutdown Delay 20 seconds 180, 300, 600
seconds
This function sets the interval between
the time when the UPS receives a shut-
down command and actual shutdown.
Synchronized
Turn-on Delay
0 seconds 60, 180, 300
seconds
The UPS will wait the specified time
after the return of utility power before
turn-on (to avoid branch circuit over-
load).