USER CONFIGURABLE ITEMS

NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE, OPTIONAL HARDWARE, OR

CONFIGURATION IN TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

Automatic Self-

Every 14 days

Every 7 days

This function sets the interval at which the

Test

(336 hours)

(168 hours),

UPS will execute a self-test. Refer to your

 

 

On Startup Only,

software manual for details.

 

 

No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight charac-

Use this field to uniquely identify the UPS

 

 

ters to define the

for network management purposes.

 

 

UPS

 

 

 

 

 

Date of Last Bat-

Manufacture

Date of Battery

Reset this date when you replace the battery

tery Replacement

Date

Replacement

pack.

 

 

 

 

Minimum Capacity

0 percent

15, 25, 35, 50, 60,

The UPS will charge its batteries to the

Before Return from

 

75, 90 percent

specified percentage before return from a

Shutdown

 

 

shutdown.

 

 

 

 

Duration of Low

2 minutes

5, 7, 10, 12, 15, 18,

This function sets the time before shutdown

Battery Warning

 

20 minutes

at which the UPS issues a low battery

 

 

 

warning. Set it higher than the default if the

 

 

 

operating system needs more time for shut-

 

 

 

down.

 

 

 

 

Alarm Delay After

5 second delay

30 second delay, At

Set the alarm delay to avoid alarms for

Line Fail

 

Low Battery Condi-

minor power glitches.

 

 

tion, No Alarm

 

 

 

 

 

Shutdown Delay

20 seconds

0, 60, 120, 240, 480,

This function sets the interval between

 

 

720, 960 seconds

when the UPS receives a shutdown com-

 

 

 

mand and when shutdown occurs.

 

 

 

 

Synchronized

0 seconds

20, 60, 120, 240,

The UPS will wait the specified time after

Turn-on Delay

 

480, 720, 960 sec-

the return of utility power before turn-on

 

 

onds

(for example, to avoid branch circuit over-

 

 

 

load).

 

 

 

 

Output Voltage

230 VAC

240, 220, 225 VAC

Nominal output voltage setting.

Setting

 

 

 

 

 

 

 

High Transfer

+ 10% of output

+5%, +15%, +20%

Maximum voltage that the UPS will pass to

Point

voltage setting

 

the load during internal bypass operation.

 

 

 

 

Low Transfer Point

-30% of output

-20%, -25%,

Minimum voltage that the UPS will pass to

 

voltage setting

-15%

the load during internal bypass operation.

 

 

 

 

990-1137A, 01/03

8

Page 10
Image 10
American Power Conversion UPS user manual User Configurable Items