NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE, OPTIONAL HARDWARE, OR

CONFIGURATION IN TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

 

CHOICES

 

 

 

Output Frequency

Automatic

50

± 3 Hz,

Sets the allowable output frequency of the

 

 

50

± 0.1 Hz,

UPS. Whenever possible, the output fre-

 

 

60

± 3 Hz,

quency tracks the input frequency. Auto-

 

 

60

± 0.1 Hz

matic setting allows 50 +/-3 or 60 +/-3 Hz

 

 

 

 

depending on the input frequency.

 

 

 

 

Unit Position

Tower

Rack Mount

The operating configuration of the UPS.

 

 

 

 

Optional Rail Kit SURTRK is required to

 

 

 

 

convert to rack mount configuration.

 

 

 

 

Number of

1

Number of con-

Defines number of battery packs for proper

Battery Packs

 

nected battery

runtime prediction. One battery pack is

 

 

packs.

equivalent to 864VAh (48V x 18Ah).

 

 

 

 

 

TERMINAL MODE

Terminal mode is a menu driven interface that allows for enhanced configuration of the UPS. This interface can be accessed using a computer and a common serial communication application, such as Hyperterminal. To enter and use the Terminal Mode:

1.Connect a computer to the UPS using the cable supplied with your UPS.

2.Launch a standard serial communication application, such as Hyperterminal.

3.Specify the communications port (comm. port) to which you have connected.

4.Set the following properties: 2400 baud, 8 data bits, no parity, one stop bit, and no flow control.

5.Press the enter or return key.

6.Follow the instructions on the screen to continue in Terminal Mode.

9

990-1137A, 01/03

Page 11
Image 11
American Power Conversion UPS user manual Terminal Mode