American Power Conversion UXI/UXICH Output Voltage Setting, 200 VAC, 208 VAC, 220 VAC, 230 VAC

Models: UXI/UXICH

1 20
Download 20 pages 56.11 Kb
Page 12
Image 12
Manual background

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

 

 

Low Bypass Point

 

Output Voltage Setting

Minimum voltage that the UPS

 

160 VAC

200 VAC:

 

will pass to connected

 

 

160 - 185 VAC

 

equipment during internal

 

 

 

bypass operation.

 

 

208 VAC:

 

 

 

 

 

 

 

160 - 190 VAC

 

 

 

 

220 VAC:

 

 

 

 

160 - 195 VAC

 

 

 

 

230 VAC:

 

 

 

 

160 - 200 VAC

 

 

 

 

240 VAC:

 

 

 

 

160 - 205 VAC

 

 

 

 

 

 

 

Output Voltage

230 VAC

200, 208, 220,

 

Allows the user to select the

 

 

230, 240 VAC

 

on-line output voltage.

 

 

 

 

 

Output Frequency

Automatic

50 ± 3 Hz

60 ± 3 Hz

Sets the allowable UPS output

 

50 ± 3 Hz or

50 ± 1 Hz

60 ± 1 Hz

frequency. Whenever possible,

 

50 ± 0.1 Hz

60 ± 0.1 Hz

the output frequency tracks the

 

60 ± 3 Hz

 

50 ± 3 Hz or 60 ± 3 Hz

input frequency.

 

 

 

 

 

 

 

Total Battery

0

0 to 1000 A h

 

Defines the Amp hours of

Capacity

 

 

 

connected battery for proper run

 

 

 

 

time prediction.

 

 

 

 

Bypass Acceptable

Not required

Required/ Not required

Phase and frequency lock

 

 

 

 

required/not required before the

 

 

 

 

UPS will switch to bypass.

 

 

 

 

 

10

Page 12
Image 12
American Power Conversion UXI/UXICH user manual Output Voltage Setting, 200 VAC, 208 VAC, 220 VAC, 230 VAC, 240 VAC