American Power Conversion UXI/UXICH Wiring must be performed by a qualified electrician

Models: UXI/UXICH

1 20
Download 20 pages 56.11 Kb
Page 4
Image 4
•Wiring must be performed by a qualified electrician.

ATTACH THE BEZEL TO THE UPS

HARDWIRING INSTRUCTIONS 5000 VA MODELS ONLY:

Wiring must be performed by a qualified electrician.

Adhere to all national and local electrical codes.

Install a high magnetic 30/32 A utility circuit breaker

Use #10 AWG gauge (5 mm2) wire.

1.Switch the utility circuit breaker OFF.

2.Remove the input access panel.

3.Remove circular knockout.

4.Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not included).

5.Replace the access panel.

2

Page 4
Image 4
American Power Conversion UXI/UXICH user manual Wiring must be performed by a qualified electrician