Operation – Display Messages/Troubleshooting

Display message

Meaning

Corrective action

 

 

 

Load Is No Longer

The load previously exceeded the

No corrective action necessary.

Above Alarm Threshold.

alarm threshold and the situation has

 

 

been corrected either because the load

 

 

decreased or the threshold was

 

 

increased.

 

 

 

 

Load Power Is Above

The load has exceeded the user-

Option 1: Use the display interface to

Alarm Limit.

specified load alarm threshold.

raise the alarm threshold.

 

 

Option 2: Reduce the load.

 

 

 

Mains Not Available.

The frequency or voltage is out of

Correct the input voltage to provide

Input Freq/Volt Out of

acceptable range for normal

acceptable voltage or frequency.

Range.

operation.

 

 

 

 

Min Runtime Restored.

The system runtime dropped below

No corrective action necessary.

 

the configured minimum and has

 

 

been restored. Additional Battery

 

 

Modules were installed, the existing

 

 

Battery Modules were recharged, the

 

 

load was reduced, or the threshold

 

 

was decreased.

 

 

 

 

No Batteries Are

No battery power is available.

Check that batteries are inserted

Connected.

 

properly.

 

 

 

Number of Battery

One or more battery modules were

No corrective action necessary.

Modules Decreased.

removed.

 

 

 

 

Number of Battery

One or more battery modules were

No corrective action necessary.

Modules Increased.

added.

 

 

 

 

Replace Batt(s).

One or more Battery Modules need

Refer to Module Replacement section

 

replacement (only applicable with

for procedures.

 

internal batteries).

 

 

 

 

Runtime Is Below Alarm

The predicted runtime is lower than

Option 1: Allow the battery modules

Threshold.

the user-specified minimum runtime

to recharge.

 

alarm threshold. Either the battery

Option 2: If possible, increase the

 

capacity has decreased, or the load

number of battery modules.

 

has increased.

Option 3: Reduce load.

 

 

Option 4: Decrease alarm threshold.

 

 

Contact APC Customer Support.

 

 

See rear cover.

 

 

 

Site Wiring Fault.

Wrong phase rotation on the input

An electrician should check that the

 

side. The UPS will continue to supply

UPS has been wired properly.

 

conditioned power, but bypass is

 

 

unavailable.

 

 

 

 

Shutdown Due To Low

The UPS was in Battery Operation

No corrective action necessary.

Battery.

and shut down the load when no more

Note: If the problem reoccurs, con-

 

battery power was available.

sider increasing the battery capacity.

 

 

 

Static Bypass Switch

The Static Bypass Switch has failed.

Contact APC Customer Support. See

Fault.

 

rear cover.

 

 

 

18

Smart-UPS® VT 10-30 kVA, 208/220 V and XR Battery Enclosure Operation Manual 990-1599B

Page 26
Image 26
American Power Conversion XR, Smart-UPS VT operation manual Operation Display Messages/Troubleshooting

XR, Smart-UPS VT specifications

The American Power Conversion (APC) Smart-UPS VT,XR is a premier uninterruptible power supply (UPS) design tailored for critical power applications. This advanced UPS system is specifically engineered for medium to large data centers and IT equipment that require high availability and robust protection against power disturbances. With its scalable architecture and cutting-edge technologies, the Smart-UPS VT,XR guarantees both performance and efficiency.

One of the standout features of the Smart-UPS VT,XR is its modular design. This allows users to expand the system's capacity as their power requirements grow, making it a flexible solution for evolving business needs. The modularity reduces upfront investment and aids in easy upgrades without significant downtime. The system supports hot-swappable batteries, which ensure that continuous power is maintained even during battery replacement.

The Smart-UPS VT,XR is equipped with multi-level battery management technology. This advanced feature optimally charges and discharges batteries to enhance their overall lifespan and performance. The UPS employs a unique Eco Mode, which improves energy efficiency by providing high-efficiency operation while maintaining reliable backup power. This not only reduces operational costs but also lowers the system's carbon footprint.

In terms of connectivity, the Smart-UPS VT,XR features an intuitive LCD touch screen interface for real-time monitoring and administration. Users can easily access important metrics such as runtime, load, and battery health, thereby improving maintenance management. Furthermore, it incorporates advanced communication options that facilitate integration with network management systems, ensuring seamless operation and monitoring across remote locations.

The power factor capability of the Smart-UPS VT,XR is also noteworthy, supporting a power factor of up to 1.0. This characteristic allows for maximum utilization of the UPS capacity, which is essential for powering modern high-density equipment. Additionally, the UPS supports a wide input voltage range and frequency tolerance, accommodating diverse power environments and ensuring reliability in various installations.

Overall, the APC Smart-UPS VT,XR stands out as a top-tier UPS solution for businesses seeking unyielding performance and efficiency. Its combination of modularity, advanced battery management, energy-saving features, and robust connectivity options makes it an invaluable asset for any mission-critical environment. Whether in a data center, telecommunications hub, or hospital, the Smart-UPS VT,XR promises reliability and peace of mind in power management.