10 Troubleshooting

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualified service person in the diagnosis of a problem and the corrective action to be taken. This troubleshooting guide can only be used by a qualified service technician.

Symptom

Possible Cause

Corrective Action

1. After repeated trig-

a. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode

gering of the piezo

 

wire is properly connected, replace the ignitor.

button, the spark ignitor

 

 

b. Defective pilot or

Using a match, light the pilot. If the pilot lights, turn off the pilot and trig-

will not light the pilot.

misaligned electrode

ger the piezo button again. If the pilot lights, an improper gas/air mixture

 

 

(spark at electrode).

caused the bad lighting and a longer purge period is recommended. If

 

 

the pilot will not light, ensure the gap at the electrode and pilot is one-

 

 

eighth (1/8) inch to have a strong spark. If the gas is OK, replace the

 

 

pilot.

 

c. No gas or low gas

Check the remote shut-off valve from the appliance. Usually, there is a

 

pressure.

valve near the gas main. There can be more that one (1) valve from the

 

 

appliance and the main.

 

d. No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2. The pilot will not stay

a. Defective thermo-

Check that the pilot flame impinges on the thermocouple. Clean and /or

lit after carefully follow-

couple.

adjust the pilot for maximum flame impingement.

ing the lighting instruc-

 

 

tions.

 

Ensure that the thermocouple connection at the gas valve is fully

 

 

inserted and tight (hand tighten plus 1/4 turn).

 

 

Disconnect the thermocouple from the valve, place one millivolt lead

 

 

wire on the tip of the thermocouple and the other meter wire on the ther-

 

 

mocouple copper lead. Start the pilot and hold the valve knob in. If the

 

 

millivolt reading is less than 15mV, replace the thermocouple.

 

b. Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty

 

 

valve.

3. The pilot is burning,

a. ON/OFF switch or

Check the ON/OFF switch and wires for proper connections. Place the

there is no gas to the

wires defective.

jumper wires across the terminals at the switch. If the burner comes on,

burner, the valve knob is

 

replace the defective switch. If the switch is OK, place the jumper wires

in the ON position, and

 

across the switch wires at the gas valve. IF the burner comes on, the

the ON/OFF switch is in

 

wires are faulty or connections are bad.

the ON position.

 

 

b. Thermopile may

If the pilot flame is not close enough physically to the thermopile, adjust

 

not be generating

the pilot flame.

 

sufficient millivoltage.

Be sure the wire connections from the thermopile at the gas valve ter-

 

 

 

 

minals are tight and that the thermopile is fully inserted into the pilot

 

 

bracket.

 

 

Check the thermopile with a millivolt meter. Take the reading at TH-

 

 

TP&TP terminals of the gas valve. The meter should read 325 millivolts

 

 

minimum, while holding the valve knob depressed in the pilot position,

 

 

with the pilot lit, and the ON/OFF switch in the OFF position. Replace

 

 

the faulty thermopile if the reading is below the specified minimum.

 

 

With the pilot in the ON position, disconnect the thermopile leads from

 

 

the valve. Take a reading at the thermopile leads. The reading should

 

 

be 325 millivolts minimum. Replace the thermopile if the reading is

 

 

below the minimum.

January 28, 2008

Quadra-Fire · Sapphire · 250-7233E

Page 41

Page 41
Image 41
Quadra-Fire SAPPH-D-CWL, 839-1460, 839-1390, SAPPH-D-CSB, 839-1440 Troubleshooting, Symptom Possible Cause Corrective Action